beautypg.com

Installation diagram, Electrical connections, Disconnect voltage adjustment – Blue Sea Systems 7635 m-LVD Low Voltage Disconnect User Manual

Page 2: Lvd connection table, Lvd normal operation status chart, Remote control switch

background image

Installation Diagram

COMMON BUSBAR

REMOTE

CONTROL

SWITCH

OPTIONAL

ALARM

STEREO OR OTHER

12V DC DEVICES

BATTERY

LED OUTPUT

OPTIONAL BATTERY SWITCH

Required if

the battery is

over 800 Cold

Cranking Amps (CCA)

ALARM OUTPUT

1
2
3

8

7
4
5
6

10A FUSE

FUSE*

See Wire Size

and Fuse

Rating Chart

above

FUSE

Connection Legend

DC Positive
DC Negative (Ground)

Optional
Control

+

-

NEG

POS

FUSE

m

-LVD Connections

Function

A

Battery

B

Load

1

Ground

2

Remote Switch

3

Alarm Output

4

LED Output

• The Installation Diagram illustrated below represents a common installation and is

not meant to be a guide for wiring a specific vessel.

Caution: Disconnect battery connections before beginning the installation.

Reconnect after the installation is complete.
Use the wire sizing chart below to select the appropriate wire sizes. Consult an

ABYC certified electrician for proper fuse placement and sizing.

* Larger wire sizes may be required to minimize voltage drop in long wire runs.

For more information please use the Circuit Wizard at www.circuitwizard.bluesea.com.

Wire Size and Fuse Rating Chart*

Amps

Min. Wire Size*

(AWG)

Fuse Rating

Min. Wire Size*

(Metric)

≤30

#10

40A-50A

6 mm²

≤50

#8

60A-65A

10 mm²

≤65

#6

90A-100A

16 mm²

Electrical Connections

m

-LVD Connection Table

Disconnect Voltage Adjustment

Disconnect Voltage LED Flash Count

Factory Default:

12.1V

5

11.9V

4

11.7V

3

11.5V

2

11.3V

1

• Press and hold the OVERRIDE position of the remote control

switch for 10 seconds to enter adjustment mode. Adjustment

mode can only be entered in the Connected or Disconnected

states, not in the Low Voltage Warning state. LED will

begin a flash pattern to indicate the current Disconnect

voltage setting (see table below).

Disconnect Voltage Adjustment Table

• Press and release OFF to decrease the Disconnect

voltage setting in 0.2V increments down to a minimum of 11.3V (1 flash).
• Press and release OVERRIDE to increase the Disconnect

voltage in 0.2V increments up to a maximum of 12.1V (5 flashes).
• When you are satisfied with your selection, release the switch, and wait

approximately 20 seconds, the

m

-LVD will save the new Disconnect

Voltage Setting, and automatically return to normal operation.

m

-LVD Normal Operation Status Chart

LED

Alarm

Relay

Status

OFF Solid

OFF

Closed

Connected

ON Solid

ON

Closed

Low Voltage Warning

Double Flash

OFF

Open

Disconnected

m

-LVD Normal Operation Status Chart

Operation during Low Voltage Warning or when Disconnected

Press OVERRIDE

to temporarily delay circuit disconnect for 10 minutes.

• Press

OVERRIDE or OFF

to silence alarm (optional alarm required).

• Press

OFF

to temporarily disconnect circuits until voltage rises.

Remote Control Switch