Installation diagram, Electrical connections, Disconnect voltage adjustment – Blue Sea Systems 7635 m-LVD Low Voltage Disconnect User Manual
Page 2: Lvd connection table, Lvd normal operation status chart, Remote control switch
Installation Diagram
COMMON BUSBAR
REMOTE
CONTROL
SWITCH
OPTIONAL
ALARM
STEREO OR OTHER
12V DC DEVICES
BATTERY
LED OUTPUT
OPTIONAL BATTERY SWITCH
Required if
the battery is
over 800 Cold
Cranking Amps (CCA)
ALARM OUTPUT
1
2
3
8
7
4
5
6
10A FUSE
FUSE*
See Wire Size
and Fuse
Rating Chart
above
FUSE
Connection Legend
DC Positive
DC Negative (Ground)
Optional
Control
+
-
NEG
POS
FUSE
m
-LVD Connections
Function
A
Battery
B
Load
1
Ground
2
Remote Switch
3
Alarm Output
4
LED Output
• The Installation Diagram illustrated below represents a common installation and is
not meant to be a guide for wiring a specific vessel.
Caution: Disconnect battery connections before beginning the installation.
Reconnect after the installation is complete.
Use the wire sizing chart below to select the appropriate wire sizes. Consult an
ABYC certified electrician for proper fuse placement and sizing.
* Larger wire sizes may be required to minimize voltage drop in long wire runs.
For more information please use the Circuit Wizard at www.circuitwizard.bluesea.com.
Wire Size and Fuse Rating Chart*
Amps
Min. Wire Size*
(AWG)
Fuse Rating
Min. Wire Size*
(Metric)
≤30
#10
40A-50A
6 mm²
≤50
#8
60A-65A
10 mm²
≤65
#6
90A-100A
16 mm²
Electrical Connections
m
-LVD Connection Table
Disconnect Voltage Adjustment
Disconnect Voltage LED Flash Count
Factory Default:
12.1V
5
11.9V
4
11.7V
3
11.5V
2
11.3V
1
• Press and hold the OVERRIDE position of the remote control
switch for 10 seconds to enter adjustment mode. Adjustment
mode can only be entered in the Connected or Disconnected
states, not in the Low Voltage Warning state. LED will
begin a flash pattern to indicate the current Disconnect
voltage setting (see table below).
Disconnect Voltage Adjustment Table
• Press and release OFF to decrease the Disconnect
voltage setting in 0.2V increments down to a minimum of 11.3V (1 flash).
• Press and release OVERRIDE to increase the Disconnect
voltage in 0.2V increments up to a maximum of 12.1V (5 flashes).
• When you are satisfied with your selection, release the switch, and wait
approximately 20 seconds, the
m
-LVD will save the new Disconnect
Voltage Setting, and automatically return to normal operation.
m
-LVD Normal Operation Status Chart
LED
Alarm
Relay
Status
OFF Solid
OFF
Closed
Connected
ON Solid
ON
Closed
Low Voltage Warning
Double Flash
OFF
Open
Disconnected
m
-LVD Normal Operation Status Chart
Operation during Low Voltage Warning or when Disconnected
•
Press OVERRIDE
to temporarily delay circuit disconnect for 10 minutes.
• Press
OVERRIDE or OFF
to silence alarm (optional alarm required).
• Press
OFF
to temporarily disconnect circuits until voltage rises.
Remote Control Switch