Recommended installation diagram, Dimension drawings wire size and fuse ratings – Blue Sea Systems 7611 BatteryLink Automatic Charging Relay - 12V/24V DC 120A User Manual
Page 2

980011740 Rev.002
425 Sequoia Drive
Bellingham, WA 98226 USA
p 360.738.8230
p 800.222.7617 USA and Canada
f 360.734.4195
www.bluesea.com
Recommended Installation Diagram
* This installation diagram shows a typical application only. Your application may differ.
For further information, please go to www.bluesea.com and navigate to
Resources/Application Briefs and Technical Briefs.
* Because the BatteryLink™ ACR is Dual Sensing, terminals A and B are interchangeable.
ACR function will not be affected by reversal of the starting and house batteries versus
the diagram.
* It is recommended that the ACR be connected directly to your battery positive terminals
through appropriately sized fuses. Connecting in a different location such as a battery
switch may affect accuracy because of voltage drop along current carrying conductors.
* If you are not knowledgeable about electrical systems, please consult an electrical
professional for help with installation.
LEGEND
Positive
Negative
Optional
Fuse
10A
16 AWG
start
run
accessory
off
Start Key Switch
2A
Optional
Remote LED
Auxiliary Battery Priority
Optional Connection
See Wire Size and Fuse Rating Chart for
connections of Terminals A and B.
NOTE: To determine wire sizes and fuse
ratings for all other wires illustrated
please visit the Circuit Wizard at
circuitwizard.bluesea.com
2A
16 AWG
16 AWG
Auxiliary
Battery
Start
Solenoid
Start
Battery
850 CCA* Maximum
* Cold Cranking Amperes
Dimension Drawings
Wire Size and Fuse Ratings
* Larger wire sizes may be required to minimize voltage drop in long wire runs.
For more information please use the Circuit Wizard at www.circuitwizard.bluesea.com
Wire Size and Fuse Rating Chart (Metric)
Charging Amps Minimum Wire Size* Fuse Rating
≤50
10 mm²
75-80A
≤70
16 mm²
80-90A
≤90
25 mm²
125-130A
≤110
35 mm²
150A
≤120
50 mm²
150-175A
Wire Size and Fuse Rating Chart (AWG)
Charging Amps Minimum Wire Size*
Fuse Rating
≤60
#6
75-90A
≤80
#4
100-125A
≤100
#2
150A
≤120
#1
175A