• Mode Sheet (continued)

MODE DESCRIPTION PARAMETERS

EXPLANATION

15

Trip 2 Type

Range = 0 - 7
0 - near
1 - exclusive
2 - hysteresis near
3 - far
4 - inclusive
5 - hysteresis far
6 - disable
7 - loss of echo
Default = 0

16

4mA*

Units = Mode 1
Range = 0 - 9999
Default = 3.00

17

20mA*

Units = Mode 1
Range = 0 - 9999
Default = 4.00

18

4mA Trim

Range = 0 - 9999
Default = 5200

19

20mA Trim

Range = 0 - 9999
Default = 9208

20

Offset

Range = 0 - 9999
Default = 0

21

Offset Polarity

Range = neg, pos
Default = neg

22

Calibration

Range = 0 - 9999

Above the

Default = 1

Decimal Point

23

Calibration

Range = 0 - 9999

Below the

Default = 0

Decimal Point

Selects the output type for Trip 2.

Sets the end point for the 4 mA
analog limit.

Sets the end point for the 20 mA
analog limit.

Fine tunes the 4 mA analog output.
(calibrated at the factory)

Fine tunes the 20 mA analog output.
(calibrated at the factory)

Sets an offset for the display.

Selects the direction of the offset.
Add or Subtract the offset from the
distance before displaying.

Sets the integer portion of the
calibration factor.

Sets the fractional portion of the
calibration factor. (decimal point is
assumed, 9999