DCU-1104 and DCU-1108

Rev. A2, 11/06

26

Automation Products Group, Inc.

APG...Providing tailored solutions for measurement applications

Tel: 1/888/525-7300 • Fax: 1/435/753-7490 • www.apgsensors.com • [email protected]

• Mode Sheet (continued)

MODE DESCRIPTION PARAMETERS

EXPLANATION

9

Loss of Echo

Units = seconds

Delay

Range=0-9999
Default = 5

10

Trip 1 Begin

Units = Mode 1
Range = 0 - 9999
Default = 3.00

11

Trip 1 End

Units = Mode 1
Range = 0 - 9999
Default = 4.00

12

Trip 1 Type

Range = 0 - 7
0 - near
1- exclusive
2 - hysteresis near
3 - far
4 - inclusive
5 - hysteresis far
6 - disable
7 - loss of echo
Default = 0

13

Trip 2 Begin

Units = Mode 1
Range = 0 - 9999
Default = 3.50

14

Trip 2 End

Units = Mode 1
Range = 0 - 9999
Default = 4.50

Set the delay in seconds before the
output will show a loss of echo
condition.

Sets the BEGIN point for Trip 1
Relay output.

Sets the END point for Trip 1 Relay
output.

Selects the output type for Trip 1.

Sets the BEGIN point for Trip 2
Relay output.

Sets the END point for Trip 2 Relay
output.