beautypg.com

Utilities (continued) – APG LPU-2127 user manual User Manual

Page 16

background image

LPU-2127

Rev. A5, 1/14

16

Automation Products Group, Inc.

APG...Providing tailored solutions for measurement applications

Tel: 1/888/525-7300 • Fax: 1/435/753-7490 • www.apgsensors.com • [email protected]

Utilities (Continued)

MODE DESCRIPTION PARAMETERS

14

Blanking

Units = Determined by Mode 1
Range = 0.5 -16 ft.
Default = 1.00 ft.

Mode 14 sets the blanking distance. The blanking distance is the zone from

the sensor to a point where the first echo will be accepted. Because of the
physical properties of an ultrasonic sensor, objects cannot be detected closer
than approximately 1 foot from the face of the transducer. This distance varies
according to how much energy is being transmitted (Mode 5) and the
installation. Low pulses and soft mounting may allow target detection as close
as 6 inches. The blanking distance can also be used to ignore unwanted targets
close to the sensor such as welds, seams, pipe fittings, or gaskets.

MODE DESCRIPTION PARAMETERS

15

Pulses

Range = 1-20
Default = 16

Mode 15 sets the maximum number of pulses the sensor can transmit when

operating in AutoSense or simply the number of pulses when operating in
manual (Mode 12). The LPU emits a burst of pulses and measures the time it
takes for the burst to travel to and from the target. The more pulses that are
sent in a burst, the stronger the returning echo. When operating in manual
mode, increase the strength of the transmission by increasing the number of
pulses for detecting soft targets in damping environments. In acoustically
active environments or small enclosed areas, decrease the number of pulses to
decrease the energy transmitted and reduce multiple echoes.

MODE DESCRIPTION

16

Software Version

Mode 16 displays the software version of the LPU.

MODE DESCRIPTION

17

Reset

Mode 17 resets the LPU to factory default settings