Calibration – APG LPU-2127 user manual User Manual

Page 13

background image

Rev. A5, 1/14

LPU-2127

13

Automation Products Group, Inc.

APG...Providing tailored solutions for measurement applications

Tel: 1/888/525-7300 • Fax: 1/435/753-7490 • www.apgsensors.com • [email protected]

Calibration

MODE

DESCRIPTION

PARAMETERS

7

4 mA Trim

Range = 0-9999
Default = 5000

Mode 7 fine tunes the minimum current sourced on the analog output.

MODE

DESCRIPTION

PARAMETERS

8

20 mA Trim

Range = 0-9999
Default = 5000

Mode 8 fine tunes the maximum current sourced on the analog output.

MODE

DESCRIPTION

PARAMETERS

9

Calibration

Range = 0-1999
Default = 1000

Mode 9 is used to calibrate the sensor for variations in the speed of sound

due to variations in atmospheres. The default of 1000 is used for most
applications. Assume a decimal after the first digit.

MODE

DESCRIPTION

PARAMETERS

10

Distance Offset

Units = Mode 1
Range = -3.00 to 3.00
Default = 0

Mode 10 is used to change the zero point of the sensor.