7. Remove screws holding blower assembly to blower deck

and slide blower assembly out of furnace.

8. Clean blower wheel and motor using a vacuum with soft

brush attachment. Do not remove or disturb balance weights
(clips) on blower wheel blades. The blower wheel should
not be dropped or bent as balance will be affected.

9. If greasy residue is present on blower wheel, remove wheel

from the blower housing and wash it with an appropriate
degreaser. To remove wheel:
a. Mark blower wheel location on shaft before disassembly

to ensure proper reassembly.

b. Loosen setscrew holding blower wheel on motor shaft.

NOTE:

Mark blower mounting arms, motor, and blower housing

so motor and each arm is positioned at the same location during
reassembly.

c. Mark blower wheel orientation and cutoff plate location

to ensure proper reassembly.

d. Remove screws securing cutoff plate and remove cutoff

plate from housing.

e. Remove bolts holding motor mounts to blower housing

and slide motor and mounts out of housing. Disconnect
capacitor and ground wire attached to blower housing
before removing motor.

f. Remove blower wheel from housing.

10. Reassemble motor and blower by reversing items 9a

through 9f. Be sure to reattach ground wire.

11. Reinstall blower assembly in furnace.
12. Reinstall control box and support assembly in furnace.
13. Reconnect blower leads to furnace control and auxiliary

limit switch leads (downflow only).
Refer to furnace wiring diagram, and connect thermostat
leads if previously disconnected. (See Fig. 11.)

NOTE:

Refer to Table 1 for motor speed lead relocation if leads

were not identified before disconnection.

CAUTION:

Heating speed selection MUST be adjusted

to provide proper temperature rise as specified on the
rating plate. Failure to adjust the heating speed may
shorten heat exchanger life.

14. Reinstall internal vent pipe and enclosure on downflow

furnaces only by reversing items 3a through 3c.

NOTE:

A releasing agent such as PAM cooking spray or equiva-

lent (must not contain corn or canola oil, aromatic or halogenated
hydrocarbons or inadequate seal may occur) and RTV sealant
(G.E. 162, 6702, or Dow-Corning 738) are needed before starting
installation. DO NOT substitute any other type of RTV sealant.
G.E. 162 (P771-9003) is available through RCD in 3-oz tubes.

15. Reinstall vent connector to furnace flue collar. After fully

assembling vent connector to furnace flue collar, securely
fasten vent connector to flue collar with 2 field-supplied,
corrosion-resistant, sheet metal screws located 180 degrees
apart and midway up the collar.

16. Turn on electrical supply. Manually close blower access

door switch. Use a piece of tape to hold switch closed.
Check for proper rotation and speed changes between
heating and cooling by jumpering R to W and then R to Y
on furnace control thermostat terminals.

WARNING:

Blower access door switch opens 115-v

power to furnace control. No component operation can
occur. Caution must be taken when manually closing this
switch for service purposes. Failure to follow this warn-
ing could result in electrical shock, personal injury, or
death.

NOTE:

If thermostat terminals are jumpered before blower ac-

cess door switch is closed, blower will run for 90 sec before
beginning a heating or cooling cycle.

17. If furnace is operating properly, remove tape to release

blower access door switch, replace blower access door.

III.

CLEANING HEAT EXCHANGER

The following steps should be performed by a qualified service
technician:

NOTE:

If the heat exchangers get a heavy accumulation of soot

and carbon, they should be replaced rather than trying to clean
them thoroughly due to their intricate design. A build-up of soot
and carbon indicates that a problem exists which needs to be
corrected, such as improper adjustment of manifold pressure,
insufficient or poor quality combustion air, incorrect size, or
damaged manifold orifice(s), improper gas, or a restricted heat
exchanger. Action must be taken to correct the problem.
If it becomes necessary to clean heat exchanger because of light
dust or corrosion proceed as follows:

Fig. 6—Model 331JAV Downflow

A99092

PRESSURE
SWITCHES

VENT PIPE
ENCLOSURE

CONTROL

FLUE
COLLAR

DRAFT
SAFEGUARD
SWITCH

AUXILIARY

LIMIT

SWITCH

MANUAL
RESET
LIMIT
SWITCHES

RELIEF

BOX

MOUNTING

SCREWS

TABLE 1—SPEED SELECTOR

COLOR

SPEED

FACTORY-

ATTACHED

TO

Black

High

Cool

Yellow (When Present)

Medium High

Spare

Blue

Medium Low

Heat

Red

Low

Spare

White

Common

C

OM

Orange (When Present)

Medium

Spare