Ervice – Class1 Engine status OEM menu User Manual
Page 2
![background image](/manuals/546741/2/background.png)
2
Service Menu
S
ERVICE
M
ENU
MENU
DEG: (CLNT / OIL)
SELECT
toggles source for temperature information
MENU
SETPOINT
SELECT
LO is displayed on the
OIL
PRESSURE
display
LO ALARM
SELECT
low oil pressure alarm (0-20 PSI)
Press the select switch first and then the silence switch, hold both for 1 second and
then release select first and then silence to save data
MENU
SETPOINT
SELECT
HI is displayed on the
ENG
TEMP
display
HI ALARM
SELECT
high temperature alarm (200-250
o
F)
Press the select switch first and then the silence switch, hold both for 1 second and
then release select first and then silence to save data
MENU
SETPOINT
SELECT
LO is displayed on the
VOLTS
display
LO ALARM
SELECT
low voltage alarm (10.0-13.0 VDC)
Press the select switch first and then the silence switch, hold both for 1 second and
then release select first and then silence to save data
MENU
SETPOINT
SELECT
HI is displayed on the
VOLTS
display
HI ALARM
SELECT
high voltage alarm (13.0-17.0 VDC)
Press the select switch first and then the silence switch, hold both for 1 second and
then release select first and then silence to save data
MENU
PTO SVC
SELECT
Ack Req?
clear the PTO SVC Message
depress
SELECT
&
MENU
, release
SELECT
to save.
Display will read NS=xxxx, where xxxx indicates when the next ser-
vice is due.
To enter the Service Menu, engine RPM can not be greater than 900.
Press the switches in this sequence.
SILENCE
:
SELECT
:
SILENCE
:
SILENCE
:
MENU
Scroll through menu items by pressing the
MENU
switch.
Select items from the menu by pressing the
SELECT
switch.
After Selection, change items by pressing the
SELECT
switch.
Save information and exit from the menu by pressing the
SILENCE
switch unless noted.
* You must save any changed item before moving on in the menu!