Refer to Fig. 7 and the following instructions:
1. Slide a 3 in. round tube clamp over the non-swaged
end of 10 ft. bright aluminized tube. (One aluminized
tube per heater.)
2. Install the round tube over the swaged discharge tube
on the burner box.
3. See the illustration below for remaining tube, clamp,
and hangers.
a. Weld seam of round tube must be down.
b. Clamps must be centered over tube connections.
c. Clamp bolts must be up.
d. Clamp bolts must be tight.
-- Tighten both bolts firmly.
-- Tighten both bolts to 35 ft.-lbs.
-- Finish tightening bolts to 44-59 ft.-lbs.
4. Slide on hangers and connect to chains.
5. The tube assembly should be either hung level, or
with a downward slope away from the burner box not
exceeding 1 in. for every 10 ft. of tube.
FIG. 7
11
ROUND TUBE
WELD SEAM DOWN
CLAMP CENTERED OVER
SWAGED DISCHARGE TUBE
AND 3 IN. ROUND TUBE.
CLAMP UP
ROUND TUBE HANGERS
THIS
NOT THIS
THIS
NOT THIS
OVAL TUBE HANGERS
3 IN. ROUND TUBE
OVAL TUBE
3 IN. ROUND CLAMP
- AW060 (18 pages)
- AW325 (18 pages)
- AW250 (18 pages)
- AD250(Spark Ignition) (30 pages)
- AB250 (18 pages)
- AW250(building controller) (31 pages)
- AD250 (31 pages)
- AW250(Smart Box controller) (31 pages)
- FA-MCS-D (21 pages)
- FA-MCS (22 pages)
- COMBO-MCS (23 pages)
- AD060 (30 pages)
- 60 Classic (16 pages)
- 115 Classic (16 pages)
- 170 Classic (16 pages)
- Pilot (94 pages)
- I-17 Infraconic Spark Ignition (28 pages)
- I-17 Infraconic Spark Ignition (26 pages)
- I-3 Infraconic (26 pages)
- I-5 Infraconic (24 pages)
- I-17 Infraconic (28 pages)
- Guardian with Smart Sense - Hot Surface (60K / 100K) (31 pages)
- Guardian with Smart Sense - Spark Ignition (60K / 100K) (31 pages)
- Guardian with Smart Sense / Direct Connect - Spark Ignition (250K) (30 pages)
- 100 Tradesman Portable Forced Air (24 pages)
- 170 Tradesman Portable Forced Air (28 pages)
- 400 Tradesman Portable Forced Air (30 pages)
- Portable Gas Heaters (99 pages)
- 45-75K Tradesman (30 pages)
- HW 120 Therma Grow (28 pages)
- HW120 Plus Therma Grow (30 pages)
- 220 Therma Grow (30 pages)
- 220 Plus Therma Grow (32 pages)
- 300 Director (27 pages)
- 350 Premier Dual Fuel (33 pages)
- 80 Premier (34 pages)
- 170 Dual Fuel (30 pages)
- 350 Premier (33 pages)
- 100 Workman - Standard LP (18 pages)
- 100 Workman - NG Low Pressure (18 pages)
- 250 Norseman (18 pages)
- 200 Norseman (18 pages)
- 225 Workman (18 pages)
- 322 Norseman - Horizontal (18 pages)
- Sentinel Radiant Tube AT150 40' Center Mount (32 pages)