XIV.

FINAL CHECKS

IMPORTANT:

Before leaving job, be sure to do the following:

1. Ensure that all wiring and tubing is secure in unit before

adding panels and covers. Securely fasten all panels and
covers.

2. Tighten service valve stem caps to 1/12-turn past finger

tight.

3. Leave User’s Manual with owner. Explain system operation

and periodic maintenance requirements outlined in manual.

4. Fill out Dealer Installation Checklist and place in customer

file.

CARE AND MAINTENANCE

For continuing high performance and to minimize possible equip-
ment failure, periodic maintenance must be performed on this
equipment. Frequency of maintenance may vary depending upon
geographic areas, such as coastal applications.

TABLE 7—TWO-SPEED COMPRESSOR

(WINDING RESISTANCE AT 70°F ± 20°)

WINDING

2 TON

3 TON

4 TON

5 TON

Start (S-C)

2.280

1.850

1.459

0.740

Run (R-C)

0.770

0.745

0.552

0.356