27 @aaca, 26 @aada 2.27 @aaca – B&B Electronics Network Device I-7011 User Manual
Page 49

49
I-7011, I-7018 User Manual
Rev:B1.0
2.27 @AACA
Description : Clear Latch Alarm
Syntax : @AACA[CHK](cr)
@
delimiter character
AA
address of setting module (00 to FF)
CA
command for clear latch alarm
Response :
Valid Command :
!AA[CHK](cr)
Invalid Command :
?AA[CHK](cr)
Syntax error or communication error may get no re-
sponse.
!
delimiter for valid command
?
delimiter for invalid command
AA
address of response module(00 to FF)
Example :
Command : @01DI
Receive : !0120101
Read address 01 digital input, return latch alarm mode, low
alarm is set.
Command : @01CA
Receive : !01
Clear address 01 latch alarm, return success.
Command : @01DI
Receive : !0120001
Read address 01 digital input, return latch alarm mode, both
alarms are clear.
Related Command :
Sec.2.21 @AADI, Sec.2.23 @AAEAT, Sec.2.26 @AADA
Related Topic :
Sec.3.6 High/Low Alarm
Note : The command is for I-7011/11D/11P/11PD only