1 %aannttccff – B&B Electronics Network Device I-7011 User Manual
Page 22

22
I-7011, I-7018 User Manual
Rev:B1.0
2.1 %AANNTTCCFF
Description : Set module Configuration
Syntax : %AANNTTCCFF[CHK](cr)
%
a delimiter character
AA
address of setting module(00 to FF)
NN
new address for setting module(00 to FF)
TT
new type for setting module (Ref Sec.1.10)
CC
new baudrate for setting module (Ref Sec.1.10)
FF
new data format for setting module (Ref Sec.1.10)
When changing the baudrate or checksum, it is neces-
sary to short the pin INIT* to ground.
Response : Valid Command :
!AA[CHK](cr)
Invalid Command :
?AA[CHK](cr)
Syntax error or communication error may get no re-
sponse.
!
delimiter for valid command
?
delimiter for invalid command. While change baudrate
or checksum setting without shorting INIT* to ground, the
module will return invalid command.
AA
address of response module(00 to FF)
Example :
Command :
%0102050600
Receive : !02
Change address from 01 to 02, return success.
Related Command :
Sec.2.7 $AA2
Related Topics :
Sec.1.10 Configuration Tables, Sec.3.1 INIT* pin Operation