Bryant 4-Way Multipoise Fixed-Capacity Direct-Vent Condensing Gas 340MAV User Manual
Page 13
INSTALLATION
I.
LEVELING LEGS (IF DESIRED)
When furnace is used in upflow position with side inlet(s), leveling
legs may be desired. (See Fig. 12.) Install field-supplied,
corrosion-resistant 5/16-in. machine bolts and nuts.
NOTE:
The maximum length of bolt should not exceed 1-1/2 in.
1. Position furnace on its back. Locate and drill a 5/16-in.
diameter hole in each bottom corner of furnace. (See Fig.
12.) Holes in bottom closure panel may be used as guide
locations.
2. For each hole, install nut on bolt and then install bolt and
nut in hole. (Install flat washer if desired.)
3. Install another nut on other side of furnace base. (Install flat
washer if desired.)
4. Adjust outside nut to provide desired height, and tighten
inside nut to secure arrangement.
NOTE:
Bottom closure must be used when leveling legs are used.
See Bottom Closure Panel section.
II.
INSTALLATION IN UPFLOW OR DOWNFLOW
APPLICATIONS
NOTE:
For downflow applications, this furnace is approved for
use on combustible flooring when special base (available from
manufacturer) Part No. KGASB0201ALL is used. Special base in
not required when this furnace is installed on manufacturer’s Coil
Assembly Part No. CD5 or CK5, or Coil Box Part No. KCAKC is
used.
1. Determine application being installed from Table 1.
2. Construct hole in floor per dimensions specified in Table 1
and Fig. 13.
3. Construct plenum to dimensions specified in Table 1 and
Fig. 13.
4. If downflow subbase (KGASB) is used, install as shown in
Fig. 14.
If coil assembly CD5 or CK5 or Coil Box KCAKC is used,
install as shown in Fig. 15.
NOTE:
Remove furnace perforated, discharge duct flanges when
they interfere with mating flanges on coil on downflow subbase.
To remove furnace perforated, discharge duct flange, use wide
duct pliers or duct flange tool to bend flange back and forth until
it breaks off. Be careful of sharp edges. (See Fig. 16.)
WARNING:
Do not bend duct flanges inward as shown
in Fig. 16. This will affect airflow across heat exchangers
and may cause limit cycling or premature heat exchanger
failure. Remove duct flange completely or bend it inward
a minimum of 210° as shown in Fig. 16.
NOTE:
For 140 size unit when installed in downflow orientation,
cut the white jumper wire off between terminals PL1-6 and PL1-9.
Refer to Fig. 24 for location of jumper. Cut jumper close to
connector and remove wire to avoid a short circuit.
Fig. 12—Leveling Legs
A89014
1
3
⁄
4
″
1
3
⁄
4
″
1
3
⁄
4
″
1
3
⁄
4
″
5
⁄
16
″
5
⁄
16
″
5
⁄
16
″
5
⁄
16
″
—13—
→