Heat pump heating performance continued – Bryant QUANTUM PLUS 650A User Manual
Page 17
![background image](/manuals/52269/17/background.png)
—17—
HEAT PUMP HEATING PERFORMANCE Continued
* The Btuh heating capacity values shown are net “integrated” values from which the defrost effect has been subtracted. The Btuh heating from supplement
heaters should be added to those values to obtain total system capacity.
† The kw values include the compressor, outdoor fan motor, and indoor blower motor. The kw from supplement heaters should be added to these values to
obtain total system kilowatts.
EDB—Entering Dry Bulb
NOTE: The performance shown includes the PressureGuard™ cycling the outdoor fan. The ambient temperature that the
outdoor fan cycles depends on the outdoor/indoor combination, indoor airflow, installation practices, and system mainte-
nance, all of which affect system performance.
INDOOR
AIR
OUTDOOR COIL ENTERING AIR TEMPERATURES °F
–3
7
17
27
37
47
57
67
EDB
CFM
Capacity
MBtuh†
Total
Pwr
Capacity
MBtuh†
Total
Pwr
Capacity
MBtuh†
Total
Pwr
Capacity
MBtuh†
Total
Pwr
Capacity
MBtuh†
Total
Pwr
Capacity
MBtuh†
Total
Pwr
Capacity
MBtuh†
Total
Pwr
Capacity
MBtuh†
Total
Pwr
Total Int* Kw† Total Int* Kw† Total Int* Kw† Total Int* Kw† Total Int* Kw† Total Int* Kw† Total Int* Kw† Total Int* Kw†
650AN048-A,C Outdoor Section With FV4ANF005 Indoor Section
65
1400
18.5 17.0 2.86 22.9 21.1 2.99 27.9 25.4 3.11 33.5 29.8 3.26 40.2 36.6 3.45 48.2 48.2 3.69 53.8 53.8 4.34 53.1 53.1 4.20
1600
18.7 17.2 2.87 23.2 21.3 2.98 28.1 25.6 3.10 33.8 30.1 3.23 40.7 37.0 3.41 48.7 48.7 3.64 54.4 54.4 4.28 53.7 53.7 4.14
1800
18.9 17.4 2.89 23.4 21.5 2.99 28.4 25.9 3.10 34.1 30.3 3.23 41.0 37.3 3.40 49.1 49.1 3.63 54.9 54.9 4.26 54.1 54.1 4.12
70
1400
18.1 16.7 3.03 22.7 20.9 3.16 27.6 25.2 3.29 33.2 29.4 3.44 39.8 36.2 3.64 47.5 47.5 3.89 54.3 54.3 4.57 52.3 52.3 4.40
1600
18.4 16.9 3.03 23.0 21.1 3.15 27.8 25.4 3.27 33.5 29.7 3.41 40.2 36.5 3.60 48.0 48.0 3.83 53.6 53.6 4.50 52.9 52.9 4.33
1800
18.6 17.1 3.05 23.2 21.3 3.16 28.1 25.6 3.27 33.8 30.0 3.41 40.5 36.9 3.58 48.4 48.4 3.81 54.1 54.1 4.47 53.3 53.3 4.31
75
1400
17.7 16.3 3.19 22.4 20.6 3.33 27.4 24.9 3.48 32.8 29.2 3.64 39.3 35.7 3.84 46.8 46.8 4.09 52.2 52.2 4.80 51.4 51.4 4.62
1600
18.0 16.6 3.20 22.7 20.9 3.33 27.6 25.2 3.46 33.1 29.4 3.60 39.7 36.1 3.79 47.4 47.4 4.04 52.8 52.8 4.72 52.0 52.0 4.54
1800
18.2 16.8 3.22 22.9 21.1 3.33 27.8 25.4 3.45 33.4 29.7 3.59 40.0 36.4 3.77 47.8 47.8 4.01 53.3 53.3 4.69 52.5 52.5 4.51
Multipliers for Determining the Performance With Other Indoor Sections
Indoor
Section
Size
Cooling
Indoor
Section
Size
Cooling
Capacity
Power
Capacity
Power
FV4ANF
005
1.00
1.00
FX4ANB
060
1.01
1.02
F(A,B)4AN(F,B,C)
060
1.02
1.10
FX4ANF
048
1.01
1.06
FB4ANB
070
1.01
1.02
CE3AA
060
1.01
1.06
FC4BN(F,B)
060
1.01
1.09
CJ5A/CK5A/CK5BA
060
1.01
1.03
FC4BNB
070
1.01
1.02
CJ5A/CK5A/CK5BN
060
1.02
1.04
FK4CNB
006
1.01
0.96
CJ5A/CK5A/CK5BX
060
1.02
1.04
FK4CNF
005
1.01
1.01
CK3BA
060
1.01
1.03
FV4ANB
006
1.01
0.96
—
—
—
650AN060-B,C Outdoor Section With FV4ANB006 Indoor Section
65
1750
24.4 22.4 3.73 30.9 28.4 3.88 37.9 34.6 4.05 45.0 40.0 4.24 52.6 47.9 4.45 60.8 60.8 4.68 58.2 58.2 4.52 56.3 56.3 4.47
2000
24.9 22.9 3.76 31.5 28.9 3.90 38.5 35.1 4.05 45.7 40.6 4.22 53.2 48.4 4.41 61.6 61.6 4.61 59.0 59.0 4.44 57.1 57.1 4.37
2250
25.3 23.3 3.80 31.9 29.3 3.93 39.0 35.5 4.06 46.2 41.0 4.23 53.7 48.9 4.39 62.2 62.2 4.58 59.6 59.6 4.39 57.8 57.8 4.31
70
1750
23.4 21.5 3.92 30.0 27.6 4.09 37.0 33.7 4.27 44.2 39.2 4.46 52.0 47.3 4.70 60.0 60.0 4.94 57.4 57.4 4.76 55.4 55.4 4.71
2000
23.8 21.9 3.95 30.5 28.0 4.10 37.6 34.3 4.26 44.8 39.8 4.44 52.5 47.8 4.65 60.7 60.7 4.87 58.1 58.1 4.67 56.2 56.2 4.60
2250
24.3 22.3 4.00 31.0 28.5 4.13 38.1 34.7 4.28 45.4 40.3 4.45 53.1 48.3 4.63 61.4 61.4 4.83 58.8 58.8 4.62 56.9 56.9 4.53
75
1750
22.2 20.5 4.12 28.9 26.6 4.30 36.0 32.9 4.49 43.2 38.4 4.70 51.3 46.7 4.96 59.2 59.2 5.21 56.5 56.5 5.02 54.5 54.5 4.95
2000
22.7 20.9 4.15 29.5 27.1 4.31 36.7 33.4 4.49 43.9 39.0 4.67 51.9 47.2 4.90 59.9 59.9 5.13 57.3 57.3 4.92 55.3 55.3 4.83
2250
23.2 21.3 4.20 30.0 27.5 4.34 37.2 33.9 4.50 44.5 39.5 4.67 52.4 47.7 4.88 60.6 60.6 5.09 57.9 57.9 4.86 56.0 56.0 4.76
Multipliers for Determining the Performance With Other Indoor Sections
Indoor
Section
Size
Cooling
Indoor
Section
Size
Cooling
Capacity
Power
Capacity
Power
FV4ANB
006
1.00
1.00
FX4ANB
060
1.00
1.03
FB4ANB
070
1.00
1.03
CC5A/CD5AW
060
0.98
1.06
FC4BNB
070
1.00
1.03
CJ5A/CK5A/CK5BX
060
0.98
1.02
FK4CNB
006
0.99
0.99
—
–
—