Detailed cooling capacities* continued – Bryant QUANTUM PLUS 650A User Manual
Page 14
—14—
DETAILED COOLING CAPACITIES* Continued
* Detailed cooling capacities are based on indoor and outdoor unit at the same elevation per ARI standard 210/240-94. If additional tubing length and/or
indoor unit is located above outdoor unit, a slight variation in capacity may occur.
† Total and sensible capacities are net capacities. Blower motor heat has been subtracted.
‡ Sensible capacities shown are based on 80°F (27°C) entering air at the indoor coil. For sensible capacities at other than 80°F (27°C), deduct 835 Btuh
(245 kw) per 1000 CFM (480 L/S) of indoor coil air for each degree below 80°F (27°C), or add 835 Btuh (245 kw) per 1000 CFM (480 L/S) of indoor coil air
per degree above 80°F (27°C).
** System kw is total of indoor and outdoor unit kilowatts.
†† At TVA rating indoor condition (75°F edb/63°F ewb). All other indoor air temperatures are at 80°F edb.
EWB—Entering Wet Bulb
EVAP
AIR
CONDENSER ENTERING AIR TEMPERATURES °F
75
85
95
105
115
125
CFM
EWB
Capacity
MBtuh†
Total
Sys
Kw**
Capacity
MBtuh†
Total
Sys
Kw**
Capacity
MBtuh†
Total
Sys
Kw**
Capacity
MBtuh†
Total
Sys
Kw**
Capacity
MBtuh†
Total
Sys
Kw**
Capacity
MBtuh†
Total
Sys
Kw**
Total Sens‡
Total Sens‡
Total Sens‡
Total Sens‡
Total Sens‡
Total Sens‡
650AN060-B,C Outdoor Section With FV4ANB006 Indoor Section
1750
72
70.1
35.6
4.43
66.6
34.4
4.92
63.1
33.1
5.47
59.2
31.7
6.07
55.0
30.3
6.73
50.2
28.7
7.42
67
64.4
45.5
4.35
61.3
44.2
4.85
58.0
42.9
5.40
54.5
41.5
6.00
50.6
40.0
6.65
46.4
38.4
7.35
63†† 60.2
44.3
4.30
57.2
43.0
4.79
54.2
41.7
5.34
50.9
40.3
5.94
47.3
38.8
6.60
43.4
37.1
7.30
62
59.2
55.1
4.29
56.4
53.7
4.78
53.5
52.3
5.33
50.5
50.4
5.93
47.5
47.5
6.60
44.2
44.2
7.32
57
57.8
57.8
4.27
55.6
55.6
4.77
53.1
53.1
5.32
50.5
50.5
5.93
47.5
47.5
6.60
44.2
44.2
7.32
2000
72
71.1
37.4
4.52
67.6
36.1
5.02
63.9
34.8
5.57
59.8
33.4
6.16
55.5
32.0
6.81
50.6
30.4
7.51
67
65.5
48.5
4.44
62.2
47.2
4.94
58.8
45.9
5.49
55.1
44.4
6.09
51.1
42.9
6.74
46.8
41.2
7.44
63†† 61.2
47.1
4.39
58.1
45.8
4.88
54.9
44.4
5.43
51.6
43.0
6.03
47.9
41.5
6.68
43.8
39.7
7.39
62
60.5
59.0
4.38
57.7
57.4
4.88
54.9
54.9
5.43
52.1
52.1
6.04
48.9
48.9
6.70
45.3
45.3
7.42
57
60.1
60.1
4.38
57.6
57.6
4.88
54.9
54.9
5.43
52.1
52.1
6.04
49.0
49.0
6.70
45.4
45.4
7.42
2250
72
72.0
39.1
4.61
68.3
37.8
5.10
64.4
36.5
5.65
60.4
35.1
6.25
55.9
33.7
6.90
50.8
32.0
7.59
67
66.2
51.4
4.53
62.9
50.1
5.03
59.4
48.7
5.57
55.6
47.3
6.17
51.7
45.7
6.83
47.1
43.9
7.53
63†† 61.9
49.8
4.48
58.8
48.5
4.97
55.6
47.1
5.52
52.1
45.6
6.12
48.3
44.0
6.77
44.1
42.1
7.48
62
61.8
61.8
4.48
59.2
59.2
4.98
56.5
56.5
5.53
53.5
53.5
6.14
50.2
50.2
6.80
46.4
46.4
7.51
57
61.8
61.8
4.48
59.2
59.2
4.98
56.4
56.4
5.53
53.4
53.4
6.14
50.2
50.2
6.80
46.4
46.4
7.51
Multipliers for Determining the Performance With Other Indoor Sections
Indoor
Section
Size
Cooling
Indoor
Section
Size
Cooling
Capacity
Power
Capacity
Power
FV4ANB
006
1.00
1.00
FX4ANB
060
0.98
1.04
FB4ANB
070
0.98
1.04
CC5A/CD5AW
060
0.97
0.99
FC4BNB
070
0.98
1.04
CJ5A/CK5A/CK5BX
060
0.97
1.00
FK4CNB
006
1.00
1.00
—
—
—