At least 36 in.

18 in. maximum

Vertical separation

between combustion

air and vent

8 3/4 in. for 3 in. kit

6 3/4 in. for 2 in. kit

Roof Te rmination (Preferred)

Abandoned masonry

used as raceway

(per code)

At least

36 in.

A

Maintain 12

in.

min. clearance above

highest anticipated

snow level, maximum of

24 in. above roof

Concentric Vent and Combustion Air

Roof Termination (preferred)

1

in.

maximum (typ) from wall to inlet

12

in.

minimum from

overhang or roof

Maintain 12

in.

min. clearance above

highest anticipated

snow level or grade

whichever is greater

A

At le

ast

36

in.

Concentric Vent

and Combustion - Air

Side Te rmination

A

At least 36 in.

Side wall termination

of less than 12

in.

above highest snow level

12

in.

min from

overhang or roof

12

in.

separation

between bottom of

combustion air and

bottom of vent (typ)

Maintain 12

in.

min. clearance above

highest anticipated

snow level or grade

whichever is greater (typ)

A

At least 36 in

.

A

Maintain 12 in. min.

clearance above

highest anticipated

snow level

Maximum of 24 in.

above roof

90°

Note: "A" denotes 0 to < 2 in.

Between the first 2 vents

Third vent must be > 36 in. away

(typ)

A05090

Fig. 36 -- Combustion Air and Vent Termination for Direct Vent (2--pipe) System

Abandoned masonry

used as raceway

(per code)

12 in. min. from

overhang or roof

Maintain 12 in.

minimum clearance

above highest anticipated

snow level or grade

whichever is greater.

Side wall termination

with 2 elbows (preferred)

12 in. min. from

overhang or roof

Maintain 12 in.

minimum clearance

above highest anticipated

snow level or grade

whichever is greater

6 in. minimum clearance

between wall and end of vent pipe.

10 in. maximum pipe length

Sidewall Termination

with Straight Pipe (preferred)

Roof Termination (Preferred)

Vent

Maintain 12 in.

minimum clearance

above highest anticipated

snow level maximum of

24 in. above roof.

90°

A05091

Fig. 37 -- Vent Pipe Termination for Ventilated Combustion Air System

355C

A