13

1. Disconnect collector box pressure tube (pink label)

attached to High Pressure Switch.

2. Use smaller diameter tube (factory--suppled in loose pars

bag) to extend tube disconnected in Item 1.

3. Route extended tube:

a. Behind inducer housing.

b. Between blower shelf and inducer housing.

4. Determine appropriate lenght, cut, and reconnect tube to

High Pressure Switch connections labeled COLLECTOR
BOX.

Condensate Trap Freeze Protection
Refer

to

Condensate

Drain

Protection

section

for

recommendations and procedures.
Construct a Working Platform
Construct working platform where all required furnace clearances
are met. (See Fig. 3 and 12 or 13.)

UNIT OPERATION HAZARD
Failure to follow this caution may result in intermittent unit

operation.
The condensate trap MUST be installed below furnace. See

Fig. 6 for dimensions. The drain connection to condensate

trap must also be properly sloped to an open drain.

CAUTION

!

NOTE: A 12--in. (304.8mm) minimum offset pipe section is
recommended with short (5 to 8 ft or 1.5 M to 2.4 M) vent
systems. This recommendation is to reduce excessive condensate
droplets from exiting the vent pipe. (See Fig. 12, 13, or 44.)

HORIZONTAL RIGHT

(SUPPLY--AIR DISCHARGE) APPLICATIONS

A horizontal right furnace application is where furnace blower is

located to the left of combustion and controls section of furnace,
and conditioned air is discharged to the right.

PROPERTY DAMAGE HAZARD
Failure to follow this caution may result in property

damage.
Local codes may require a drain pan under entire furnace

and condensate trap when a condensing furnace is used in

an attic application or over a finished ceiling.

CAUTION

!

NOTE: In Canada, installations shall be in accordance with
current NSCNGPIC and/or local codes.
NOTE: The auxiliary junction box (J--box ) MUST be relocated
to opposite side of furnace casing. (See Fig. 14.) See Electrical
Connection section for J--box relocation.

Condensate Trap Location

CAP

PLUG

COLLECTOR BOX

DRAIN TUBE (BLUE &

WHITE STRIPED)

INDUCER HOUSING

(MOLDED) DRAIN

TUBE (VIOLET)

COLLECTOR BOX TUBE (PINK)

COLLECTOR BOX

DRAIN TUBE (BLUE)

COLLECTOR BOX

EXTENSION TUBE

CONDENSATE

TRAP

COLLECTOR BOX

TUBE (GREEN)

AUXILIARY “J” BOX RELOCATED HERE

A07279

Fig. 14 -- Horizontal Right Tube Configuration

The condensate trap must be removed from the factory--installed

blower shelf location and relocated in selected application
location as shown in Fig. 2 or 14.
To relocate condensate trap from the blower shelf to desired

location, perform the following:

1. Remove three tubes connected to condensate trap.
2. Remove trap from blower shelf by gently pushing tabs

inward and rotaing trap.

CARBON MONOXIDE POISONING HAZARD
Failure to follow this warning could result in personal

injury or death.
Casing hole filler cap must be installed in blower shelf hole

when condensate trap is relocated to prevent combustion

products being drawn in from appliances in the equipment

room.

!

WARNING

3. Install casing hole filler cap (factory--supplied in loose

parts bag) into blower shelf hole where trap was removed.

4. Install condensate trap into right--hand side casing hole by

inserting tube connection stubs through casing hole an

rotating until tabls snap into locking position.

5. Fill unused condensate trap casing holes with plastic filler

caps (factory--supplied in loose parts bag).

UPFLOW OR DOWNFLOW

HORIZONTAL

FRONT

LEVEL (0″)

TO

1

2

″ MAX

MIN

1

4

TO

1

2

″ MAX

FRONT

A02146

Fig. 15 -- Proper Condensate Drainage