DOWNFLOW APPLICATIONS

A downflow furnace application is where furnace blower is
located above combustion and controls section of furnace, and

conditioned air is discharged downwards.
Condensate Trap Location
The condensate trap must be removed from the factory--installed
blower shelf location and relocated in selected application

location as shown in Fig. 2, 9, or 10.
To relocate condensate trap from the blower shelf to desired
location, perform the following:

1. Remove three tubes connected to condensate trap.
2. Remove trap from blower shelf by gently pushing tabs

inward and rotaing trap.

3. Remove casing hole filler cap from casing hole. (See Fig.

2 and 10.)

4. Install casing hole filler cap (factory--supplied in loose

parts bag) into blower shelf hole where trap was removed.

CARBON MONOXIDE POISONING HAZARD
Failure to follow this warning could result in personal

injury or death.
Casing hole filler cap must be installed in blower shelf hole

when condensate trap is relocated to prevent combustion

products being drawn in from appliances in the equipment

room.

!

WARNING

5. Install condensate trap into left--hand side casing hole by

inserting tube connection stubs through casing hole and
rotating until tabls snap into locking position.

6. Fill unused condensate trap casing holes with plastic filler

caps (factory--supplied in loose parts bag).

CAP

PLUG

COLLECTOR BOX

DRAIN TUBE (BLUE &

WHITE STRIPED)

INDUCER HOUSING

(MOLDED) DRAIN

TUBE (VIOLET)

COLLECTOR BOX

TUBE (PINK)

COLLECTOR BOX

DRAIN TUBE (BLUE)

COLLECTOR BOX

TUBE EXTENSION

CONDENSATE

TRAP

COLLECTOR BOX

TUBE (GREEN)

COLLECTOR BOX

EXTENSION

DRAIN TUBE

DRAIN TUBE

COUPLING

A07277

Fig. 10 -- Factory--Shipped Trap Location

(Shown with Blower Access Panel Removed)

Condensate Trap Tubing
NOTE
: See Fig. 9 or 10 or tube routing label on main furnace
door to check for proper connections.

1. Collector Box DrainTube

a. Remove factory--installed plug from LOWER collector

box drain tube (blue and white striped label).

b. Install removed clamp and plug into UPPER collector

box drain tube (blue label) which was connected to

condensate trap.

c. Connect LOWER collector box drain connection to

condensate trap.

(3.) Condensate Trap Located on Left Side of Casing

(a.)Connect LOWER collector box drain tube (blue

and white striped label) to condensate trap.
Tube does not need to be cut.

(b.)Clamp tube to prevent any condensate leakage.

(4.) Condensate Trap Located on Right Side of Casing

(a.)Install drain tube coupling (factory--supplied in

loose parts bag) into collector box drain tube
(blue and white striped label) which was

previously plugged.

(b.)Connect

larger

diameter

drain

tube

(factory--supplied in loose parts bag) to drain
tube coupling, extending collecor box drain tube
for connection to condensate trap.

(c.)Route extended collector box drain tube

between gas valve and inlet housing as shown in

Fig. 10.

(d.)Determine appropriate length and cut.

(e.)Connect to condensate trap.

2. Inducer Housing Drain Tube

a. Remove factory--installed cap and clamp from LOWER

inducer housing drain connection.

355C

A

V