UNIT

ELECTRICAL CHARACTERISTICS

UNIT WEIGHT

CENTER OF GRAVITY

IN. [MM]

lb

kg

X

Y

Z

042

208-230-1-60, 208/230-3-60

297

135

355.6 (14.00)

508.0 (20.00)

304.8 (12.00)

048

208/230-1-60, 208/230-3-60

310

141

355.6 (14.00)

508.0 (20.00)

304.8 (12.00)

Fig. 3—Base Unit Dimensions, 564A 042,048

C00003

REQUIRED CLEARANCE FOR OPERATION AND SERVICING

INCHES [mm]

CONDENSER

.

COIL ACCESS SIDE..............................................

30.00 [762.0]

POWER ENTRY SIDE....................................................................30.00 [762.0]
(EXCEPT FOR NEC REQUIREMENTS)
UNIT TOP .......................................................................................48.00 [1219.2]
SIDE OPPOSITE DUCTS ..............................................................30.00 [762.0]

LEGEND

NEC – National Electrical Code

NOTES:
1. Clearances must be maintained to prevent recirculation of air from outdoor-

fan discharge, with the exception of the condenser coil (36.00 in [914.0 mm]. A
removable fence or barricade requires no clearance.

2. Dimensions are in inches. Dimensions in [ ] are in millimeters.

REQUIRED CLEARANCE TO COMBUSTIBLE MATL.

INCHES [mm]

TOP OF UNIT .........................................................................................0
DUCT SIDE OF UNIT.............................................................................0
SIDE OPPOSITE DUCTS ......................................................................0
BOTTOM OF UNIT .................................................................................0

NEC. REQUIRED CLEARANCES.

INCHES [mm]

BETWEEN UNITS, POWER ENTRY SIDE ....................................42.00 [1066.8]
UNIT AND UNGROUNDED SURFACES, POWER ENTRY SIDE .36.00 [914.0]
UNIT AND BLOCK OR CONCRETE WALLS AND OTHER
GROUNDED SURFACES, POWER ENTRY SIDE.........................42.00 [1066.8]

—3—