COOLING

On a call for cooling, the compressor contactor (C) and the IFR are
energized through the Y and G terminals of the thermostat. On
units with a compressor time-delay relay, there is a 5-minute (

±

45

sec) delay between compressor starts. Energizing the compressor
contactor supplies power to the compressor and the outdoor
(condenser) fan motor (OFM). Energizing the IFR provides power
to the IFM.

When the need for cooling has been satisfied, the OFM, compres-
sor, and IFM (FAN on AUTO) are deenergized. If the unit is

equipped with a 30-second delay, the indoor fan will remain
energized for 30 seconds after the compressor is deenergized (030
and 060 units only).

C.

HEATING

If accessory electric heaters are installed, on a call for heat the
thermostat energized the W relay which energizes the electric
heaters. The IFR is energized which starts the indoor-fan motor. If
the heaters are staged, W2 is energized when the second stage of
heating is required. When the need for heating is satisfied, the
heater and IFM are deenergized.

Fig. 17—Cooling Charging Chart, 564A036 Units

C00017

°

OUTDOOR TEMP

°

F

°

C

115

46

45

7

55

13

65

18

75

24

95

35

105

41

85

29

Fig. 18—Cooling Charging Chart, 564A042 Units

C00018

°

OUTDOOR TEMP

°

F

°

C

115

46

45

7

55

13

65

18

75

24

95

35

105

41

85

29

Fig. 19—Cooling Charging Chart, 564A048 Units

C00019

°

OUTDOOR TEMP

°

F

°

C

115

46

45

7

55

13

65

18

75

24

95

35

105

41

85

29

Fig. 20—Cooling Charging Chart, 564A060 Units

C00020

°

OUTDOOR TEMP

°

F

°

C

115

46

125

52

45

7

55

13

65

18

75

24

95

35

105

41

85

29

—13—