beautypg.com

Bryant AIR CONDITIONERS 564A User Manual

Page 14

background image

MAINTENANCE

To ensure continuing high performance, and to reduce the possi-
bility of premature equipment failure, periodic maintenance must
be performed on this equipment. This cooling unit should be
inspected at least once each year by a qualified service person. To
troubleshoot cooling of units, refer to Troubleshooting chart in
back of book.

NOTE TO EQUIPMENT OWNER: Consult your local dealer
about the availability of a maintenance contract.

WARNING:

The ability to properly perform mainte-

nance on this equipment requires certain expertise, me-
chanical skills, tools and equipment. If you do not possess
these, do not attempt to perform any maintenance on this
equipment, other than those procedures recommended in
the User’s Manual. FAILURE TO HEED THIS WARN-
ING COULD RESULT IN SERIOUS INJURY, DEATH
OR DAMAGE TO THIS EQUIPMENT.

The minimum maintenance requirements for this equipment are as
follows:

1. Inspect air filter(s) each month. Clean or replace when

necessary.

2. Inspect indoor coil, outdoor coil, drain pan, and condensate

drain each cooling season for cleanliness. Clean when
necessary.

TABLE 4—DRY COIL AIR DELIVERY* HORIZONTAL DISCHARGE

(DEDUCT 10% FOR 208 VOLT OPERATION)

230 AND 460 VOLT

Unit

Motor Speed

Air Delivery

External Static Pressure (in. wg)

0.1

0.2

0.3

0.4

0.5

0.6

0.7

0.8

0.9

024

Low

Watts

288

285

282

279

274

268

261

-

-

Cfm

875

820

802

734

668

582

478

-

-

Med

Watts

390

383

378

369

360

350

340

-

-

Cfm

1131

1090

1038

978

917

830

721

-

-

High

Watts

528

520

510

495

480

460

450

-

-

Cfm

1391

1338

1285

1200

1115

1018

920

-

-

030

Low

Watts

288

285

282

279

274

268

261

-

-

Cfm

875

820

802

734

668

582

478

-

-

Med

Watts

390

383

378

369

360

350

340

-

-

Cfm

1131

1090

1038

978

917

830

721

-

-

High

Watts

528

520

510

495

480

460

450

-

-

Cfm

1891

1338

1285

1200

1115

1018

920

-

-

036

Low

Watts

450

435

420

400

380

335

326

311

-

Cfm

1231

1218

1204

1120

1008

950

863

751

-

Med

Watts

470

450

445

410

388

359

338

321

-

Cfm

1302

1264

1205

1163

1081

940

873

783

-

High

Watts

660

635

610

575

540

505

485

460

-

Cfm

1700

1660

1581

1450

1297

1190

1095

999

-

042

Low

Watts

478

458

440

411

378

350

327

317

-

Cfm

1303

1270

1224

1179

1126

1022

911

816

-

Med

Watts

481

468

450

438

404

370

338

320

735

Cfm

1310

1280

1241

1181

1110

1022

943

811

-

High

Watts

-

798

678

647

618

578

540

500

-

Cfm

-

1736

1688

1618

1510

1421

1309

1187

1060

048

Low

Watts

-

-

801

760

730

688

650

600

570

Cfm

-

-

1898

1841

1757

1682

1564

1429

1365

High

Watts

-

-

870

842

818

782

696

632

628

Cfm

-

-

2000

1903

1799

1718

1625

1446

1333

060†

2 Speed

Low

Watts

890

850

810

790

735

680

580

480

422

Cfm

1834

1820

1791

1762

1703

1640

1415

1159

950

Med

Watts

1040

1018

1000

950

890

835

790

650

580

Cfm

2230

2102

2025

1960

1901

1855

1752

1468

1121

High

Watts

1073

1038

1001

958

896

840

800

691

575

Cfm

2230

2202

2160

2122

2052

1926

1791

1588

1202

060

3 Speed

Low

Watts

1058

1008

942

891

860

828

750

700

630

Cfm

2384

2200

2197

2071

1989

1889

1820

1729

1640

Med

Watts

1266

1086

1021

1002

977

924

860

819

700

Cfm

2724

2476

2392

2344

2262

2132

2001

1910

1820

High

Watts

1301

1216

1197

1127

1058

1011

979

869

870

Cfm

2760

2618

2543

2423

2292

2169

2056

1943

1832

* Air delivery values are based on operating voltage of 230 v or 460 v, dry coil, without filter or electric heater. Deduct wet coil, filter and electric heater pressure drops to

obtain external static pressure available for ducting.

See Tables 5-7.

†460-v motors have 2 or 3 speeds (size 060 only).

NOTES:
1. Do not operate the unit at a cooling airflow that is less than 350 cfm for each 12,000 Btuh of rated cooling capacity. Evaporator coil frosting may occur at airflows below

this point.

2. Dashes indicate portions of the table that are beyond the blower motor capacity or are not recommended.

TABLE 5—WET COIL PRESSURE DROP

UNIT SIZE

564A

AIRFLOW

(CFM)

PRESSURE DROP

(IN. WG)

024

600

0.02

700

0.05

800

0.06

900

0.07

030

900

0.06

1000

0.06

1200

0.08

036

1000

0.07

1200

0.09

1400

0.11

1600

0.12

042

1000

0.04

1200

0.06

1400

0.08

1600

0.09

048

1400

0.07

1600

0.08

1800

0.09

060

1700

0.07

1800

0.08

2100

0.09

2300

0.10

—14—