574d, 20 table 6 – cooling charging chart, Table 7 – filter pressure drop table (in. wc) – Bryant 574D User Manual

Page 20

background image

20

Table 6 – Cooling Charging Chart

75 (24)

85 (29)

95 (35)

105 (41)

115 (46)

Pressure

(psig)

5

10

15

20

25

Pressure

(kPa)

3

6

8

11

14

018

13 (7.2)

14 (7.8)

15 (5.0)

16 (8.9)

16 (8.9)

189

66

61

56

51

46

41

1303

19

16

13

11

8

5

024

10 (5.6)

11 (6.1)

11 (6.1)

12 (6.7)

13 (7.2)

196

68

63

58

53

48

43

1351

20

17

15

12

9

6

030

12 (6.7)

13 (7.2)

14 (7.8)

15 (5.0)

15 (5.0)

203

71

66

61

56

51

46

1399

21

19

16

13

10

8

036

14 (7.8)

14 (7.8)

14 (7.8)

14 (7.8)

14 (7.8)

210

73

68

63

58

53

48

1448

23

20

17

14

11

9

042

11 (6.1)

11 (6.1)

11 (6.1)

10 (5.6)

9 (5.0)

217

75

70

65

60

55

50

1496

24

21

18

15

13

10

048

8 (4.4)

7 (3.9)

7 (3.9)

7 (3.9)

6 (3.3)

224

77

72

67

62

57

52

1544

25

22

19

16

14

11

060

14 (7.8)

13 (7.2)

12 (6.7)

11 (6.1)

10 (5.6)

231

79

74

69

64

59

54

1593

26

23

20

18

15

12

238

81

76

71

66

61

56

1641

27

24

21

19

16

13

245

82

77

72

67

62

57

1689

28

25

22

20

17

14

252

84

79

74

69

64

59

1737

29

26

23

21

18

15

260

86

81

76

71

66

61

1792

30

27

25

22

19

16

268

88

83

78

73

68

63

1848

31

29

26

23

20

17

276

90

85

80

75

70

65

1903

32

30

27

24

21

19

284

92

87

82

77

72

67

1958

33

31

28

25

22

20

292

94

89

84

79

74

69

2013

35

32

29

26

23

21

300

96

91

86

81

76

71

2068

36

33

30

27

24

22

309

98

93

88

83

78

73

2130

37

34

31

28

26

23

318

100

95

90

85

80

75

2192

38

35

32

29

27

24

327

102

97

92

87

82

77

2254

39

36

33

31

28

25

336

104

99

94

89

84

79

2316

40

37

34

32

29

26

345

106

101

96

91

86

81

2378

41

38

35

33

30

27

354

108

103

98

93

88

83

2440

42

39

36

34

31

28

364

110

105

100

95

90

85

2509

43

40

38

35

32

29

374

112

107

102

97

92

87

2578

44

41

39

36

33

30

384

113

108

103

98

93

88

2647

45

42

40

37

34

31

394

115

110

105

100

95

90

2716

46

44

41

38

35

32

404

117

112

107

102

97

92

2785

47

45

42

39

36

33

414

119

114

109

104

99

94

2854

48

46

43

40

37

34

424

121

116

111

106

101

96

2923

49

47

44

41

38

35

434

123

118

113

108

103

98

2992

50

48

45

42

39

36

444

124

119

114

109

104

99

3061

51

48

46

43

40

37

454

126

121

116

111

106

101

3130

52

49

47

44

41

38

464

128

123

118

113

108

103

3199

53

50

48

45

42

39

474

129

124

119

114

109

104

3268

54

51

48

46

43

40

484

131

126

121

116

111

106

3337

55

52

49

47

44

41

494

132

127

122

117

112

107

3406

56

53

50

47

45

42

504

134

129

124

119

114

109

3475

57

54

51

48

46

43

514

136

131

126

121

116

111

3544

58

55

52

49

46

44

524

137

132

127

122

117

112

3612

58

56

53

50

47

45

534

139

134

129

124

119

114

3681

59

56

54

51

48

45

4- Refer to the required Subcooling in the table based on the model size and
the Outdoor Ambient temperature.

1- Measure Discharge line pressure by attaching a gauge to the service port.

2- Measure the Liquid line temperature by attaching a temperature sensing
device to it.

3- Insulate the temperature sensing device so that the Outdoor Ambient
doesn’t affect the reading.

9 - Remove charge if the measured temperature is lower than the table value.

Model Size

Required Subcooling oF (oC)

Outdoor Ambient Temperature

Required Liquid Line Temperature for a Specific Subcooling (R-410A)

Required Subcooling (

o

C)

Required Subcooling (

o

F)

50ES500006 REV 2.0

6- Find the Pressure Value in the table corresponding to the the measured
Pressure of the Compressor Discharge line.

8- Add Charge if the measured temperature is higher than the table value.

7- Read across from the Pressure reading to obtain the Liquid line
temperature for a required Subcooling

Charging Procedure

5- Interpolate if the Outdoor ambient temperature lies in between the table
values.

Table 7 – Filter Pressure Drop Table (in. wc)

FILTER SIZE

CFM

500

600

700

800

900 1000 1100 1200 1300 1400 1500 1600 1700 1800 1900 2000 2100 2200 2300

20X20X1

0.05 0.07 0.08

0.1

0.12 0.13 0.14 0.15

24X30X1

0.04 0.05 0.06 0.07 0.07 0.08 0.09

0.1

24X36X1

0.06 0.07 0.07 0.08 0.09 0.09 0.10 0.11 0.12 0.13 0.14 0.14

Table 8 – Dry Coil Air Delivery* -- Horizontal and Downflow Discharge --

Unit 574D024--060 (Deduct 10% for 208 Volts)

Unit

Heating Rise

Range

o

F (°C)

Motor

Speed

External Static Pressure (in. wc)

0.1

0.2

0.3

0.4

0.5

0.6

0.7

0.8

0.9

574D018040

30 --- 60

(17 --- 33)

Low

1

Watts

260

243

229

217

209

--- ---

--- ---

--- ---

--- ---

CFM

859

775

667

536

382

--- ---

--- ---

--- ---

--- ---

Heating Rise

o

F

°C

35

19

39

22

45

25

56

31

NA

NA

NA

NA

NA

High

Watts

340

328

317

307

300

294

--- ---

--- ---

--- ---

CFM

1064

948

820

680

528

364

--- ---

--- ---

--- ---

Heating Rise

o

F

°C

NA

32

18

37

20

44

25

57

32

NA

NA

NA

NA

574D024040

20 --- 50

(11 --- 28)

Low

1

Watts

311

309

304

301

286

290

286

280

--- ---

CFM

935

885

820

757

686

583

423

263

--- ---

Heating Rise

o

F

°C

32

18

34

19

37

20

40

22

44

24

NA

NA

NA

NA

Medium

Watts

411

405

398

390

379

357

357

345

327

CFM

1195

1155

1100

1028

957

868

769

647

365

Heating Rise

o

F

°C

25

14

26

14

27

15

29

16

31

17

35

19

39

22

46

26

NA

High

Watts

528

518

509

492

477

467

447

435

421

CFM

1484

1421

1368

1279

1185

1088

970

853

712

Heating Rise

o

F

°C

20

11

21

12

22

12

23

13

25

14

28

15

31

17

35

20

42

23

574D