beautypg.com

Warning, Start--up, Step 1 — check for refrigerant leaks – Bryant 574D User Manual

Page 13: Step 2 — start--up heating and make adjust- ments

background image

13

FIRE, EXPLOSION HAZARD
Failure to follow this warning could result in personal

injury, death or property damage.
Do not purge gas supply into the combustion chamber. Do

not use a match or other open flame to check for gas leaks.

!

WARNING

4. Verify the following conditions:

a. Make sure gas line is free of air. Before lighting the unit

for the first time, perform the following with the gas
valve in the OFF position:

NOTE: If the gas supply pipe was not purged before connecting
the unit, it will be full of air. It is recommended that the ground
joint union be loosened, and the supply line be allowed to purge
until the odor of gas is detected. Never purge gas lines into a
combustion chamber. Immediately upon detection of gas odor,
retighten the union. Allow 5 minutes to elapse, then light unit.

b. Make sure that condenser--fan blade is correctly

positioned in fan orifice. Top 1/3 of condenser--fan
blade should be within fan orifice venturi.

c. Ensure fan hub is positioned correctly with respect to

motor housing (See Fig. 12).

d. Make sure that air filter(s) is in place.

e. Make sure that condensate drain trap is filled with water

to ensure proper drainage.

f. Make sure that all tools and miscellaneous loose parts

have been removed.

FAN GRILLE

MOTOR

1/8" MAX BETWEEN

MOTOR AND FAN HUB

MOTOR SHAFT

1/2ý

C99009

Fig. 12 -- Fan Blade Clearance

START--UP

Step 1 — Check for Refrigerant Leaks

Proceed as follows to locate and repair a refrigerant leak and to

charge the unit:

1. Locate leak and make sure that refrigerant system pressure

has been relieved and reclaimed from both high-- and
low--pressure ports.

2. Repair leak following accepted practices.

NOTE: Install a filter drier whenever the system has been opened
for repair.

3. Add a small charge of Puron (R--410A) refrigerant vapor to

system and leak--test unit.

4. Recover refrigerant from refrigerant system and evacuate to

500 microns if no additional leaks are found.

5. Charge unit with Puron (R--410A) refrigerant, using a

volumetric charging cylinder or accurate scale. Refer to unit
rating plate for required charge.

Step 2 — Start--up Heating and Make Adjust-

ments

Complete the required procedures given in the Pre--Start--Up

section before starting the unit. Do not jumper any safety devices

when operating the unit. Make sure that burner orifices are

properly aligned. Unstable operation my occur when the burner
orifices in the manifold are misaligned.
Follow the lighting instructions on the heating section operation
label (located inside the burner or blower access door) to start the

heating section.
NOTE: Make sure that gas supply has been purged, and that all
gas piping has been checked for leaks.

MANIFOLD

PIPE PLUG

C99019

Fig. 13 -- Burner Assembly

MANIFOLD

BURNER

BURNER FLAME

C99021

Fig. 14 -- Monoport Burner

CHECK HEATING CONTROL

Start and check the unit for proper heating control operation as

follows (see furnace lighting instructions located inside burner or
blower access panel):

1. Place room thermostat SYSTEM switch in the HEAT

position and the fan switch is placed in AUTO position.

2. Set the heating temperature control of the thermostat above

room temperature.

3. The induced--draft motor will start.
4. After a call for heating, the main burner should light within

5 sec. If the burners do not light, there is a 22--sec. delay

before another 5--sec. try. If the burners still do not light,
this sequence is repeated. If the burners do not light within

15 minutes from the initial call for heat, there is a lockout.
To reset the control, break the 24--v power to W.

5. The evaporator fan will turn on 45 sec. after the flame has

been established. The evaporator fan will turn off 45 sec.
after the thermostat has been satisfied.

574D