General information, I: general information – Burnham HF SERIES User Manual
Page 5
5
I: General Information
Figure 1: HF Packaged Boiler (HF-98/HF-173)
Notes:
1.
2.
3.
4.
5.
Firing rates based on 140,000 BTU per gallon of oil
IBR net water ratings based on a pick-up allowance of 1.15
Manufacturer should be consulted before selecting a boiler for installations having
unusual piping and pick-up requirements.
Firebox draft setting: -.02 inches water column
Ratings based on 13.0% CO
2
Ta ble 1 :
WAT ER RAT ING S AN D S PEC IFI C ATI O NS
Descr iption
HF- 98
HF- 122
HF- 147
HF- 173
DO E Heating Capac ity ( MB H)
104
132
154
184
IBR Net Water rating ( MB H)
90
115
134
160
Fir ing Ra te (gal/hr )
.85
1.10
1.25
1.50
Noz zle Spec ifi cation
.75 x 45° B
.90 x 45° B
1.00 x 45° B
1.25 x 45° B
Stac k Dia meter (inc h)
6
6
7
7
Nu mber of Tub es
12
12
18
18
Boiler Water Cap. ( gal.)
20
20
40
40
Supply S ize ( FPT)
1¼
1¼
2
2
Retur n S ize ( FPT)
1¼
1¼
2
2
Tankles s Heater S ize (gal/mi n)
4 (5 Optiona l)
4 (5 Optiona l)
5
5
Chimn ey S ize (mi n)
8" x 8" x 15'
8" x 8" x 15'
8" x 8" x 15'
8" x 8" x 15'
Appr ox. S hipping Wt. ( lb.)
450
450
720
720
DIM ENSIO N S M ax . W orki ng P re s su re : 30 PSI (W ate r O nly)
A Over all W idth ( in.)
18-1/8
18-1/8
24
24
B Over all Len gth Boiler ( in.)
24-1/2
24-1/2
31-3/4
31-3/4
C J ack et Height ( in.)
37-3/4
37-3/4
46-3/4
46-3/4
D J ack et Length ( in.)
18
18
21-3/4
21-3/4
E Jac ket W idth ( in.)
18-1/8
18-1/8
22
22
F S mok e Outlet Height ( in.)
25-1/4
25-1/4
30
30
G O ver all Leng th w/Burner ( in.)
33
33
39
39