IV. Service and Cleaning

A

. General. Inspection, service and cleaning should be

conducted annually. Turn off electric power and close
oil supply valve while conducting service or mainte-
nance.

B

. Firetubes and Combustion Chamber.

1. CLEAN THE FIRETUBES

a. For access to fireside of boiler, remove fasteners

holding flue box panel closed.

b. Using a 1 1/2" diameter wire brush (30" handle),

clean firetubes.

c. Remove fasteners holding burner door. Carefully

remove door with burner still attached.

2. CLEAN THE COMBUSTION CHAMBER

Using wire or fiber bristle brush, clean inside of
combustion chamber.

3. AFTER CLEANING

a. Vacuum debris inside combustion chamber and

vacuum remaining fireside of boiler as necessary.

NOTICE

B UR NER S H U TD O WN : O p e n S e rv ic e

Switch to turn off burner.

Manual Oil Supply Valve should be closed

and Electric Service to boiler turned off if

boiler will not be operated for an extended

period of time.