beautypg.com

Bryant 564B User Manual

Page 5

background image

VII.

INSTALL ELECTRICAL CONNECTIONS

WARNING: ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal
injury or death.
The unit cabinet must have an uninterrupted, unbroken
electrical ground to minimize the possibility of personal
injury if an electrical fault should occur. This ground may
consist of an electrical wire connected to the unit ground
in the control compartment, or conduit approved for
electrical ground when installed in accordance with NEC
(National Electrical Code), ANSI (American National
Standards Institute)/NFPA (latest edition) (in Canada,
Canadian Electrical Code CSA C22.1) and local electrical
codes.

CAUTION: UNIT DAMAGE HAZARD
Failure to follow these precautions may result in damage
to the unit being installed:
1. Make all electrical connections in accordance with

NEC ANSI/NFPA (latest edition) and local electrical
codes governing such wiring. In Canada, all electrical
connections must be in accordance with CSA standard
C22.1 Canadian Electrical Code Part 1 and applicable
local codes. Refer to unit wiring diagram.

2. Use only copper conductor for connections between

field-supplied electrical disconnect switch and unit.
DO NOT USE ALUMINUM WIRE.

3. Be sure that high-voltage power to unit is within

operating voltage range indicated on unit rating plate.

4. Insulate low-voltage wires for highest voltage con-

tained within conduit when low-voltage control wires
are run in same conduit as high-voltage wires.

5. Do not damage internal components when drilling

through any panel to mount electrical hardware, con-
duit, etc. Consult local power company for correction
of improper voltage.

A.

HIGH-VOLTAGE CONNECTIONS

The unit must have a separate electrical service with a field-
supplied, waterproof disconnect switch mounted at, or within sight
from the unit. Refer to the unit rating plate for maximum
fuse/circuit breaker size and minimum circuit amps (ampacity) for
wire sizing. See Table 6 for electrical data.

The field-supplied disconnect may be mounted on the unit over the
high-voltage inlet hole. (See Fig. 2.)

TABLE 2—PHYSICAL DATA

UNIT 564B

024

030

036

042

048

060

OPERATING WEIGHT (lbs)

268

299

352

364

359

408

COMPRESSOR TYPE

Scroll

Ultra Tech Scroll

REFRIGERANT Charge (lb)

R-22

6.8

9.5

9.5

11.1

10.7

12.5

REFRIGERANT METERING DEVICE

Orifice ID (in.)

Accurater

TXV

.067

.067

.082

.086

Orifice OD (in.)

.049

.057

.059

.063

.070

.073

CONDENSER COIL

Rows...Fins/in.

Face Area (sq. ft.)

Copper Tubes, Aluminum Plate Fins

2...21

11.1

2...21

12.7

2...21

15.8

2...21

15.8

2...21

13.3

2...21

15.8

CONDENSER FAN

Nominal Cfm

Diameter (in.)

Motor HP (RPM)

Propeller

2600

20

1/8 (825)

2600

20

1/8 (825)

3200

20

1/4 (1100)

3200

20

1/4 (1100)

3200

20

1/4 (1100)

3300

20

1/2 (1100)

EVAPORATOR COIL

Face Area (sq. ft.)

Copper Tubes, Aluminum Plate Fins

3...17

4.3

3...17

4.9

4...17

4.9

4...17

6.1

4...17

4.9

4...17

6.1

Evaporator Blower

Nominal Airflow (CFM)

Size (in.)

Motor HP (RPM)

Direct Drive

800

10 x 8

1/2 (1050)

1000

10 x 8

1/2 (1050)

1200

11 x 9

3/4 (1050)

1400

11 x 9

3/4 (1050)

1600

11 x 10

1 (1050)

1875

11 x 10

1 (1050)

CONNECTING DUCT SIZES

Supply Air (in.)

Return Air (in.)

Round

14

14

Return-Air Filters (in.)*

Throwaway

24 x 24

24 x 24

24 x 24

24 x 30

30 x 30

30 x 30

*Required filter sizes shown are based on the ARI (Air Conditioning and Refrigeration Institute) rated airflow at a velocity of 300 ft/min for throwaway type or 450 ft/min for

high capacity type. Recommended filters are 1-in. thick.

—5—