Bryant 564B User Manual
Page 5
![background image](/manuals/48516/5/background.png)
VII.
INSTALL ELECTRICAL CONNECTIONS
WARNING: ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal
injury or death.
The unit cabinet must have an uninterrupted, unbroken
electrical ground to minimize the possibility of personal
injury if an electrical fault should occur. This ground may
consist of an electrical wire connected to the unit ground
in the control compartment, or conduit approved for
electrical ground when installed in accordance with NEC
(National Electrical Code), ANSI (American National
Standards Institute)/NFPA (latest edition) (in Canada,
Canadian Electrical Code CSA C22.1) and local electrical
codes.
CAUTION: UNIT DAMAGE HAZARD
Failure to follow these precautions may result in damage
to the unit being installed:
1. Make all electrical connections in accordance with
NEC ANSI/NFPA (latest edition) and local electrical
codes governing such wiring. In Canada, all electrical
connections must be in accordance with CSA standard
C22.1 Canadian Electrical Code Part 1 and applicable
local codes. Refer to unit wiring diagram.
2. Use only copper conductor for connections between
field-supplied electrical disconnect switch and unit.
DO NOT USE ALUMINUM WIRE.
3. Be sure that high-voltage power to unit is within
operating voltage range indicated on unit rating plate.
4. Insulate low-voltage wires for highest voltage con-
tained within conduit when low-voltage control wires
are run in same conduit as high-voltage wires.
5. Do not damage internal components when drilling
through any panel to mount electrical hardware, con-
duit, etc. Consult local power company for correction
of improper voltage.
A.
HIGH-VOLTAGE CONNECTIONS
The unit must have a separate electrical service with a field-
supplied, waterproof disconnect switch mounted at, or within sight
from the unit. Refer to the unit rating plate for maximum
fuse/circuit breaker size and minimum circuit amps (ampacity) for
wire sizing. See Table 6 for electrical data.
The field-supplied disconnect may be mounted on the unit over the
high-voltage inlet hole. (See Fig. 2.)
TABLE 2—PHYSICAL DATA
UNIT 564B
024
030
036
042
048
060
OPERATING WEIGHT (lbs)
268
299
352
364
359
408
COMPRESSOR TYPE
Scroll
Ultra Tech Scroll
REFRIGERANT Charge (lb)
R-22
6.8
9.5
9.5
11.1
10.7
12.5
REFRIGERANT METERING DEVICE
Orifice ID (in.)
Accurater
TXV
.067
.067
.082
.086
—
—
Orifice OD (in.)
.049
.057
.059
.063
.070
.073
CONDENSER COIL
Rows...Fins/in.
Face Area (sq. ft.)
Copper Tubes, Aluminum Plate Fins
2...21
11.1
2...21
12.7
2...21
15.8
2...21
15.8
2...21
13.3
2...21
15.8
CONDENSER FAN
Nominal Cfm
Diameter (in.)
Motor HP (RPM)
Propeller
2600
20
1/8 (825)
2600
20
1/8 (825)
3200
20
1/4 (1100)
3200
20
1/4 (1100)
3200
20
1/4 (1100)
3300
20
1/2 (1100)
EVAPORATOR COIL
Face Area (sq. ft.)
Copper Tubes, Aluminum Plate Fins
3...17
4.3
3...17
4.9
4...17
4.9
4...17
6.1
4...17
4.9
4...17
6.1
Evaporator Blower
Nominal Airflow (CFM)
Size (in.)
Motor HP (RPM)
Direct Drive
800
10 x 8
1/2 (1050)
1000
10 x 8
1/2 (1050)
1200
11 x 9
3/4 (1050)
1400
11 x 9
3/4 (1050)
1600
11 x 10
1 (1050)
1875
11 x 10
1 (1050)
CONNECTING DUCT SIZES
Supply Air (in.)
Return Air (in.)
Round
14
14
Return-Air Filters (in.)*
Throwaway
24 x 24
24 x 24
24 x 24
24 x 30
30 x 30
30 x 30
*Required filter sizes shown are based on the ARI (Air Conditioning and Refrigeration Institute) rated airflow at a velocity of 300 ft/min for throwaway type or 450 ft/min for
high capacity type. Recommended filters are 1-in. thick.
—5—