beautypg.com

Bryant 564B User Manual

Page 9

background image

3. Insulate the temperature sensing device so that the outdoor

ambient doesn’t affect the reading.

4. Locate the measured suction line pressure in the top row of

Table 8 and the measured outdoor ambient temperature in
the left column of the table. Based on the two values,
determine the required suction line temperature.

5. If the measured suction line temperature is greater than the

tabulated temperature, add charge in the system.

048 and 060 units:

1. Measure discharge line pressure by attaching a gauge to the

service port.

2. Measure the liquid line temperature by attaching a tempera-

ture sensing device to it.

3. Insulate the temperature sensing device so that the outdoor

ambient doesn’t affect the reading.

4. Refer to the required subcooling in Tables 4 and 5 to find

the required subcooling based on the model size and the
outdoor ambient temperature.

5. Interpolate if the outdoor temperature lies in between the

table values. Extrapolate if the temperature lies beyond the
table range.

6. Find the pressure value corresponding to the measured

pressure on the compressor discharge line.

7. Read across from the pressure reading to obtain the Liquid

line temperature for a required subcooling.

8. Add charge if the measured temperature is higher than the

liquid line temperature value in the table.

9. Add charge using the service connection on the suction line

of the compressor.

IV.

INDOOR AIRFLOW AND AIRFLOW ADJUSTMENTS

NOTE: For cooling operation, the recommended airflow is 350 to
450 cfm per each 12,000 Btuh of rated cooling capacity.

Table 7 shows dry coil air delivery for horizontal discharge units.
Tables 9-11 show pressure drops.

NOTE: Be sure that all supply- and return-air grilles are open,
free from obstructions, and adjusted properly.

WARNING: ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal
injury or death.
Disconnect electrical power to the unit and install lockout
tag before changing blower speed.

Airflow can be changed by changing the 24 volts lead connections
of the blower motor.

Unit 564B blower motors are factory wired for rated airflow
operation.

A.

FOR 208/230-V BLOWER MOTORS

The motor lead speed connections are as follows:

SIZE

RATED AIRFLOW

HIGH AIRFLOW

024

Tap 1

Tap 3

030

Tap 2

Tap 4

036

Tap 1

Tap 3

042

Tap 2

Tap 4

SIZE

RATED AIRFLOW

HIGH AIRFLOW

Low

Stage

High

Stage

Low

Stage

High

Stage

048

Tap 1

Tap 3

Tap 2

Tap 4

060

Tap 1

Tap 3

Tap 2

Tap 4

V.

UNIT CONTROLS

All compressors have the following internal-protection controls.

A.

HIGH-PRESSURE RELIEF VALVE

This valve opens when the pressure differential between the low
and high side becomes excessive.

B.

LOSS OF CHARGE SWITCH

Located on the outdoor liquid line is a low-pressure switch which
functions as a loss-of-charge switch. This switch contains a
Schrader core depressor. This switch opens at 7 psig and closes at
22 psig. No adjustment is necessary.

Unit Control
Power

Thermostat

and subbase

G

Y

W2

W3

R

RED

GREEN

YELLOW

C

BROWN

WHITE

VIOLET

A05213

Fig. 10A—Control Connections (Sizes 024-042)

Unit Control
Power

Thermostat

and subbase

G

Y1

Y2

W2

R

RED

GREEN

YELLOW

W3

PINK

BROWN

C

WHITE

VIOLET

A05214

Fig.10B—Control Connections (Sizes 048-060)

—9—