Burnham V8 Series User Manual
Page 23

23
b. Thread 1½” NPT x 15” long nipple into the 1½"
NPT x 90° elbow and tighten with a pipe wrench.
c. Thread one of the circulator fl ange onto the
nipple and tighten with a pipe wrench. Position 
fl ange so that the bolt slots are parallel to the 
boiler front.
d. Place a circular fl ange gasket in the fl ange
groove on the circulator and mount the circulator 
on the fl ange. Note that this is the return piping 
and the fl ow arrow on the circulator should point 
down Ð. Fasten circulator with 7/16” - 14 x 1½" 
long cap screws and 7/16" - 14 nuts.
e. Fasten the second circulator fl ange and gasket to
the circulator.
6. Install relief valve, as shown in Figure 1A, 1B, and
1C, onto ¾” NPT x 8” nipple previously installed in 
Paragraph H, No. 2, step b. Tighten with wrench. 
Pipe discharge as shown in Figures 13A, 13B 
and 13C. Installation of the relief valve must be 
consistent with ANSI/ASME Boiler and Pressure 
Vessel Code, Section IV.
G
N
I
N
R
A
W
e
b
t
s
u
m
g
n
i
p
i
p
e
g
r
a
h
c
s
i
d
e
v
l
a
v
y
t
e
f
a
S
f
o
l
a
i
t
n
e
t
o
p
e
t
a
n
i
m
i
l
e
o
t
r
o
o
l
f
r
a
e
n
d
e
p
i
p
a
e
r
a
y
n
a
n
i
e
p
i
p
t
o
n
o
D
.
s
n
r
u
b
e
r
e
v
e
s
l
l
a
t
s
n
i
t
o
n
o
D
.
r
u
c
c
o
d
l
u
o
c
g
n
i
z
e
e
r
f
e
r
e
h
w
.
s
p
a
c
r
o
s
g
u
l
p
,
s
e
v
l
a
v
f
f
o
-
t
u
h
s
y
n
a
7. On units without a heater opening, install the well
into the ¾” NPT tapping "A" located on the front of 
the boiler in the upper left corner. See Figures 1A 
and 5. Tighten the well and insert the control’s bulb 
into the well. Secure control to well with set screw.
G
N
I
N
R
A
W
o
t
n
i
d
e
t
r
e
s
n
i
y
l
l
u
f
e
b
t
s
u
m
b
l
u
b
t
a
t
s
a
u
q
A
.
l
l
e
w
e
h
t
8. On units with a heater opening, install the well in
the ½" NPT or ¾” NPT tapping on the tankless 
heater plate or cover plate. See Figures 1B, 1C and 
5. Tighten the well and insert the control’s bulb into 
the well. Secure control to well with set screw.
9. Connect Field Wiring.
a. Water boilers without tankless heater and with
front tankless heater. Connect the fi eld wiring 
from the circulator to the aquastat control and 
from the control to the burner disconnect J-box 
or directly to the burner J-box. Make the wiring 
connections as shown on Figures 22, 23A and 
23D.
b. Water boilers with rear tankless heater. Connect
the fi eld wiring from a standard junction box 
or burner disconnect J-box to the circulator, 
aquastat control and burner. Make the wiring 
connections as shown on Figure 23B.
NOTE:
• Do not remove (cut) "T-T" jumper on R7184P 
 Primary Control for application 9a or 9b 
 above.
c. Refer to Paragraph S for details on use of burner
disconnect junction box provided with all 
knockdown boiler builds.
P. INSTALL TRIM AND CONTROLS WITH
CARLIN 102CRD BURNER.
Follow instructions in Paragraph N, Steps 1 through 7.
Steam Boilers Only (see Figures 1D and 5).
8. Connect Field Wiring
a. Steam Boiler with Hydrolevel CG450 LWCO,
Carlin Burner.
Connect
the
fi eld wiring to the pressure limit, the
LWCO, R8239C Control Center and the burner 
disconnect J-box or directly to burner J-box on 
burners less disconnect harness (power cord). 
If equipped with tankless heater, connect fi eld 
wiring from the aquastat control to the R8239C 
Control Center’s “R-G” terminals. Make the 
wiring connections as shown in Figure 19A.
b. Steam Boiler with McDonnell & Miller 
 
PS-801 or McDonnell & Miller 67 LWCO, 
Carlin Burner.
Connect
the
fi eld wiring to the LWCO, the
pressure limit and the burner disconnect J-box. 
If equipped with tankless heater, connect fi eld 
wiring from the aquastat control to the oil burner 
primary control’s “T-T” Terminals. Make the 
wiring connections as shown in Figures 20A, and 
21A.
c. Refer to Paragraph S for details on use of burner
disconnect junction box provided with all 
knockdown boiler builds.
Water boilers Only (see Figures 1A, 1B, 1C and 5).
Follow instructions in Paragraph O, Steps 1 through 7
9. Connect Field Wiring
a. Water boilers without tankless heater and with
front tankless heater. Connect the fi eld wiring 
from the circulator to the aquastat control and 
from the control to the burner disconnect J-box 
or directly to oil burner primary control on 
burners less disconnect harness (power cord). 
Make the wiring connections as shown on 
Figures 22A and 23B .
b. Water boilers with rear tankless heater. Connect
the fi eld wiring from a standard junction box 
or burner disconnect J-box to the circulator, 
aquastat control and burner. Make the wiring 
connections as shown on Figure 23E.
c. Refer to Paragraph S for details on use of burner
disconnect junction box provided with all 
knockdown boiler builds.