3. Jumper P to P1.
4. Disconnect wires at T and T1. Place 5.6 kilo-ohm re-

sistor across T and T1.

5. Jumper TR to 1.
6. Jumper TR to N.
7. If connected, remove sensor from terminals S

O

and +.

Connect 1.2 kilo-ohm 4074EJM checkout resistor
across terminals S

O

and +.

8. Put 620-ohm resistor across terminals S

R

and +.

9. Set minimum position, DCV set point, and exhaust

potentiometers fully CCW (counterclockwise).

10. Set DCV maximum position potentiometer fully CW

(clockwise).

11. Set enthalpy potentiometer to D.
12. Apply power (24 vac) to terminals TR and TR1.

B. Differential Enthalpy

To check differential enthalpy:

1. Make sure EconoMi$er IV preparation procedure has

been performed.

2. Place 620-ohm resistor across S

O

and +.

3. Place 1.2 kilo-ohm resistor across S

R

and +. The Free

Cool LED should be lit.

4. Remove 620-ohm resistor across S

O

and +. The Free

Cool LED should turn off.

5. Return EconoMi$er IV settings and wiring to normal

after completing troubleshooting.

C. Single Enthalpy

To check single enthalpy:

1. Make sure EconoMi$er IV preparation procedure has

been performed.

2. Set the enthalpy potentiometer to A (fully CCW). The

Free Cool LED should be lit.

3. Set the enthalpy potentiometer to D (fully CW). The

Free Cool LED should turn off.

4. Return EconoMi$er IV settings and wiring to normal

after completing troubleshooting.

D. DCV (Demand Controlled Ventilation) and Power
Exhaust

To check DCV and Power Exhaust:

1. Make sure EconoMi$er IV preparation procedure has

been performed.

2. Ensure terminals AQ and AQ1 are open. The LED for

both DCV and Exhaust should be off. The actuator
should be fully closed.

3. Connect a 9-v battery to AQ (positive node) and AQ1

(negative node). The LED for both DCV and Exhaust
should turn on. The actuator should drive to between
90 and 95% open.

4. Turn the Exhaust potentiometer CW until the Ex-

haust LED turns off. The LED should turn off when
the potentiometer is approximately 90%. The actua-
tor should remain in position.

5. Turn the DCV set point potentiometer CW until the

DCV LED turns off. The DCV LED should turn off
when the potentiometer is approximately 9-v. The ac-
tuator should drive fully closed.

6. Turn the DCV and Exhaust potentiometers CCW un-

til the Exhaust LED turns on. The exhaust contacts
will close 30 to 120 seconds after the Exhaust LED
turns on.

7. Return EconoMi$er IV settings and wiring to normal

after completing troubleshooting.

E. DCV Minimum and Maximum Position

To check the DCV minimum and maximum position:

1. Make sure EconoMi$er IV preparation procedure has

been performed.

2. Connect a 9-v battery to AQ (positive node) and AQ1

(negative node). The DCV LED should turn on. The
actuator should drive to between 90 and 95% open.

3. Turn the DCV Maximum Position potentiometer to

midpoint. The actuator should drive to between 20
and 80% open.

4. Turn the DCV Maximum Position potentiometer to

fully CCW. The actuator should drive fully closed.

5. Turn the Minimum Position potentiometer to mid-

point. The actuator should drive to between 20 and
80% open.

6. Turn the Minimum Position Potentiometer fully CW.

The actuator should drive fully open.

7. Remove the jumper from TR and N. The actuator

should drive fully closed.

8. Return EconoMi$er IV settings and wiring to normal

after completing troubleshooting.

F. Supply-Air Input

To check supply-air input:

1. Make sure EconoMi$er IV preparation procedure has

been performed.

2. Set the Enthalpy potentiometer to A. The Free Cool

LED turns on. The actuator should drive to between
20 and 80% open.

3. Remove the 5.6 kilo-ohm resistor and jumper T to T1.

The actuator should drive fully open.

4. Remove the jumper across T and T1. The actuator

should drive fully closed.

5. Return EconoMi$er IV settings and wiring to normal

after completing troubleshooting.

G. EconoMi$er IV Troubleshooting Completion

This procedure is used to return the EconoMi$er IV to opera-
tion. No troubleshooting or testing is done by performing the
following procedure.

1. Disconnect power at TR and TR1.
2. Set enthalpy potentiometer to previous setting.
3. Set DCV maximum position potentiometer to previ-

ous setting.

4. Set minimum position, DCV set point, and exhaust

potentiometers to previous settings.

5. Remove 620-ohm resistor from terminals S

R

and +.

6. Remove 1.2 kilo-ohm checkout resistor from termi-

nals S

O

and +. If used, reconnect sensor from termi-

nals S

O

and +.

7. Remove jumper from TR to N.
8. Remove jumper from TR to 1.
9. Remove 5.6 kilo-ohm resistor from T and T1. Recon-

nect wires at T and T1.

10. Remove jumper from P to P1. Reconnect device at P

and P1.

11. Apply power (24 vac) to terminals TR and TR1.