beautypg.com

Bryant DURAPAC 580F User Manual

Page 20

background image

20

to enter the building. Make minimum position adjustments
with at least 10 F temperature difference between the out-
door and return-air temperatures.

To determine the minimum position setting, perform the
following procedure:

1. Calculate the appropriate mixed air temperature

using the following formula:

T

O

= Outdoor-Air Temperature

OA = Percent of Outdoor Air

T

R

= Return-Air Temperature

RA = Percent of Return Air

T

M

= Mixed-Air Temperature

As an example, if local codes require 10% outdoor air
during occupied conditions, outdoor-air temperature
is 60 F, and return-air temperature is 75 F.

(60 x .10) + (75 x .90) = 73.5 F

2. Disconnect the supply air sensor from terminals T

and T1.

3. Ensure that the factory-installed jumper is in place

across terminals P and P1. If remote damper posi-
tioning is being used, make sure that the terminals
are wired according to Fig. 22 and that the minimum
position potentiometer is turned fully clockwise.

4. Connect 24 vac across terminals TR and TR1.

5. Carefully adjust the minimum position potentiometer

until the measured mixed-air temperature matches
the calculated value.

6. Reconnect the supply air sensor to terminals T and

T1.

Remote control of the EconoMi$er IV damper is desirable
when requiring additional temporary ventilation. If a
field-supplied remote potentiometer (Honeywell part num-
ber S963B1128) is wired to the EconoMi$er IV controller, the
minimum position of the damper can be controlled from a
remote location.

To control the minimum damper position remotely, remove
the factory-installed jumper on the P and P1 terminals on
the EconoMi$er IV controller. Wire the field-supplied poten-
tiometer to the P and P1 terminals on the EconoMi$er IV
controller. See Fig. 31.

Damper Movement

Damper movement from full open to full closed (or vice
versa) takes 2

1

/

2

minutes.

Thermostats

The EconoMi$er IV control works with conventional thermo-
stats that have a Y1 (cool stage 1), Y2 (cool stage 2), W1
(heat stage 1), W2 (heat stage 2), and G (fan). The
EconoMi$er IV control does not support space temperature
sensors. Connections are made at the thermostat terminal
connection board located in the main control box.

Occupancy Control

The factory default configuration for the EconoMi$er IV con-
trol is occupied mode. Occupied status is provided by the
black jumper from terminal TR to terminal N. When unoccu-
pied mode is desired, install a field-supplied timeclock func-
tion in place of the jumper between TR and N. See Fig. 22.
When the timeclock contacts are closed, the EconoMi$er IV
control will be in occupied mode. When the timeclock con-
tacts are open (removing the 24-v signal from terminal N),
the EconoMi$er IV will be in unoccupied mode.

Demand Controlled Ventilation (DCV)

When using the EconoMi$er IV for demand controlled venti-
lation, there are some equipment selection criteria which
should be considered. When selecting the heat capacity and
cool capacity of the equipment, the maximum ventilation
rate must be evaluated for design conditions. The maximum
damper position must be calculated to provide the desired
fresh air.

Typically the maximum ventilation rate will be about 5 to
10% more than the typical cfm required per person, using
normal outside air design criteria.

A proportional anticipatory strategy should be taken with
the following conditions: a zone with a large area, varied
occupancy, and equipment that cannot exceed the required
ventilation rate at design conditions. Exceeding the required
ventilation rate means the equipment can condition air at a
maximum ventilation rate that is greater than the required
ventilation rate for maximum occupancy. A proportional-
anticipatory strategy will cause the fresh air supplied to
increase as the room CO

2

level increases even though the

CO

2

set point has not been reached. By the time the CO

2

level reaches the set point, the damper will be at maximum
ventilation and should maintain the set point.

In order to have the CO

2

sensor control the economizer

damper in this manner, first determine the damper voltage
output for minimum or base ventilation. Base ventilation is
the ventilation required to remove contaminants during
unoccupied periods. The following equation may be used to
determine the percent of outside-air entering the building for
a given damper position. For best results there should be at
least a 10 degree difference in outside and return-air
temperatures.

T

O

= Outdoor-Air Temperature

OA = Percent of Outdoor Air

T

R

= Return-Air Temperature

RA = Percent of Return Air

T

M

= Mixed-Air Temperature

Once base ventilation has been determined, set the mini-
mum damper position potentiometer to the correct position.

The same equation can be used to determine the occupied or
maximum ventilation rate to the building. For example, an

(T

O

x

OA

) + (T

R

x

RA

) = T

M

100

100

(T

O

x

OA

) + (T

R

x

RA

) = T

M

100

100

0

1000

2000

3000

4000

5000

6000

2

3

4

5

6

7

8

800 ppm

900 ppm

1000 ppm

1100 ppm

RANGE CONFIGURA

TION (ppm)

DAMPER VOLTAGE FOR MAX VENTILATION RATE

CO SENSOR MAX RANGE SETTING

2

Fig. 32 — CO

2

Sensor Maximum Range Setting