Table 6 — Fan Rpm at Motor Pulley Settings*

*Approximate fan rpm shown.

†Indicates alternate motor and drive package.

**Indicates high-static motor and drive package.

††Indicates standard motor and drive package.

Table 7 — Motor Data

LEGEND

BHP — Brake Horsepower

*Extensive motor and electrical testing on these units ensures that the full horse-

power range of the motors can be utilized with confidence. Using fan motors up
to the horsepower ratings shown in this table will not result in nuisance tripping
or premature motor failure. Unit warranty will not be affected.

†Single phase/three-phase.

NOTES:
1. All indoor-fan motors 5 hp and larger meet the minimum efficiency require-

ments as established by the Energy Policy Act of 1992 (EPACT) effective
October 24, 1997.

2. High-static motor not available on single-phase units.

Table 8 — Accessory/FIOP Static Pressure* (in. wg)

LEGEND

*The static pressure must be added to external static pressure. The sum and the

evaporator entering-air cfm should then be used in conjunction with the Fan
Performance tables to determine blower rpm and watts.

UNIT
580F

MOTOR PULLEY TURNS OPEN

0

1

/

2

1

1

1

/

2

2

2

1

/

2

3

3

1

/

2

4

4

1

/

2

5

5

1

/

2

6

036†

1045

1009

973

937

901

865

829

793

757

721

685

036**

1455

1423

1392

1360

1328

1297

1265

1233

1202

1170

1138

1107

1075

048†

1175

1135

1094

1054

1013

973

932

892

851

811

770

048**

1455

1423

1392

1360

1328

1297

1265

1233

1202

1170

1138

1107

1075

060†

1192

1166

1140

1114

1087

1061

1035

1009

983

957

930

904

878

060**

1685

1647

1608

1570

1531

1493

1454

1416

1377

1339

1300

072, 073††

1460

1421

1382

1343

1304

1265

1226

1187

1148

1109

1070

072, 073**

1685

1647

1608

1570

1531

1493

1454

1416

1377

1339

1300

UNIT
580F

EVAPORATOR-FAN

MOTOR

UNIT

VOLTAGE

MAXIMUM ACCEPTABLE

CONTINUOUS BHP*

MAXIMUM ACCEPTABLE

OPERATING WATTS

MAXIMUM

AMP DRAW

036

Standard

208/230

0.34

440

2.8

460

1.3

575

1.3

Alternate

208/230

1.20

1000

4.9

460

2.1

575

2.1

High Static

208/230

2.40

2120

6.0

460

3.0

575

3.0

048

Standard

208/230

0.75

850

3.5

460

1.8

575

1.8

Alternate

208/230

1.20

1000

4.9

460

2.1

575

2.1

High Static

208/230

2.40

2120

6.0

460

3.0

575

3.0

060

Standard

208/230

1.20

1340

5.9

460

3.2

575

3.2

Alternate

208/230

1.30/2.40†

2120

10.1/6.7†

460

3.0

575

3.0

High Static

208/230

2.90

2562

8.6

460

3.9

575

3.9

072, 073

Standard

208/230

2.40

2120

6.7

460

3.0

575

3.0

High Static

208/230

2.90

2562

8.6

460

3.9

575

3.9

COMPONENT

CFM

2250

2500

3000

3500

4000

4500

5000

Vertical EconoMi$er IV

0.06

0.075

0.115

0.15

0.195

0.25

0.325

Horizontal EconoMi$er IV

0.10

0.15

0.21

0.275

0.34

FIOP — Factory-Installed Option