Table 6 — fan rpm at motor pulley settings, Table 7 — motor data, Table 8 — accessory/fiop static pressure* (in. wg) – Bryant DURAPAC 580F User Manual
Page 23

—
23
—
Table 6 — Fan Rpm at Motor Pulley Settings*
*Approximate fan rpm shown.
†Indicates alternate motor and drive package.
**Indicates high-static motor and drive package.
††Indicates standard motor and drive package.
Table 7 — Motor Data
LEGEND
BHP — Brake Horsepower
*Extensive motor and electrical testing on these units ensures that the full horse-
power range of the motors can be utilized with confidence. Using fan motors up
to the horsepower ratings shown in this table will not result in nuisance tripping
or premature motor failure. Unit warranty will not be affected.
†Single phase/three-phase.
NOTES:
1. All indoor-fan motors 5 hp and larger meet the minimum efficiency require-
ments as established by the Energy Policy Act of 1992 (EPACT) effective
October 24, 1997.
2. High-static motor not available on single-phase units.
Table 8 — Accessory/FIOP Static Pressure* (in. wg)
LEGEND
*The static pressure must be added to external static pressure. The sum and the
evaporator entering-air cfm should then be used in conjunction with the Fan
Performance tables to determine blower rpm and watts.
UNIT
580F
MOTOR PULLEY TURNS OPEN
0
1
/
2
1
1
1
/
2
2
2
1
/
2
3
3
1
/
2
4
4
1
/
2
5
5
1
/
2
6
036†
1045
1009
973
937
901
865
829
793
757
721
685
—
—
036**
1455
1423
1392
1360
1328
1297
1265
1233
1202
1170
1138
1107
1075
048†
1175
1135
1094
1054
1013
973
932
892
851
811
770
—
—
048**
1455
1423
1392
1360
1328
1297
1265
1233
1202
1170
1138
1107
1075
060†
1192
1166
1140
1114
1087
1061
1035
1009
983
957
930
904
878
060**
1685
1647
1608
1570
1531
1493
1454
1416
1377
1339
1300
—
—
072, 073††
1460
1421
1382
1343
1304
1265
1226
1187
1148
1109
1070
—
—
072, 073**
1685
1647
1608
1570
1531
1493
1454
1416
1377
1339
1300
—
—
UNIT
580F
EVAPORATOR-FAN
MOTOR
UNIT
VOLTAGE
MAXIMUM ACCEPTABLE
CONTINUOUS BHP*
MAXIMUM ACCEPTABLE
OPERATING WATTS
MAXIMUM
AMP DRAW
036
Standard
208/230
0.34
440
2.8
460
1.3
575
1.3
Alternate
208/230
1.20
1000
4.9
460
2.1
575
2.1
High Static
208/230
2.40
2120
6.0
460
3.0
575
3.0
048
Standard
208/230
0.75
850
3.5
460
1.8
575
1.8
Alternate
208/230
1.20
1000
4.9
460
2.1
575
2.1
High Static
208/230
2.40
2120
6.0
460
3.0
575
3.0
060
Standard
208/230
1.20
1340
5.9
460
3.2
575
3.2
Alternate
208/230
1.30/2.40†
2120
10.1/6.7†
460
3.0
575
3.0
High Static
208/230
2.90
2562
8.6
460
3.9
575
3.9
072, 073
Standard
208/230
2.40
2120
6.7
460
3.0
575
3.0
High Static
208/230
2.90
2562
8.6
460
3.9
575
3.9
COMPONENT
CFM
2250
2500
3000
3500
4000
4500
5000
Vertical EconoMi$er IV
0.06
0.075
0.115
0.15
0.195
0.25
0.325
Horizontal EconoMi$er IV
—
0.10
0.15
0.21
0.275
0.34
—
FIOP — Factory-Installed Option