beautypg.com

American Power Conversion MX28B200 User Manual

Page 39

background image

MX28B200/400 –48 VDC User’s Manual (990-9133)

Page 33

PARAMETER NAME/

[MENU LOCATION]

DESCRIPTION

DISPLAY SCREENS /

DEFAULT SETTINGS

OEM S Offset
Security Level {2}
[OEM]

Current offset adjustment for factory
calibration of battery current
readings/settings.

OEM S Offset m+
0.0 A

Output Relay 1 Alarm
Security Level {1}
[SYSTEM/OUT-RLY/RLY-
MAP]



Output Relay 6 Alarm
Security Level {1}
[SYSTEM/OUT-RLY/RLY-
MAP]

Output Relay 1 Alarm can be “mapped”
to activate other output relays (“Ignore”
activates no additional relays).




Output Relay 6 Alarm can be “mapped”
to activate other output relays (“Ignore”
activates no additional relays).

Out-Rly 1 Alm m+
Ignore




Out-Rly 6 Alm m+
Ignore

Output Relay 1 Alias
Security Level {1}
[SYSTEM/OUT-RLY/ALIAS]



Output Relay 6 Alias {1}
[SYSTEM/OUT-RLY/ALIAS]

An alternate name (alias) can be
assigned to Output Relay 1 if desired.



An alternate name (alias) can be
assigned to Output Relay 6 if desired.

Out-Rly 1 m+
Relay 1



Out-Rly 6 m+
Relay 6

Output Relay 1 Delay
Security Level {1}
[SYSTEM/OUT-RLY/RLY-
MAP]



Output Relay 6 Delay
Security Level {1}
[SYSTEM/OUT-RLY/RLY-
MAP]

Delay between sensing of the alarm
condition and activation of Output Relay
1. An alarm condition must exist for
longer than the delay to be activated.


Delay between sensing of the alarm
condition and activation of Output Relay
6. An alarm condition must exist for
longer than the delay to be activated.

Out-Rly 1 Dly m+
0 sec



Out-Rly 6 Dly m+
0 sec

Output Relay Major Alias
Security Level {1}
[SYSTEM/OUT-RLY/ALIAS]

An alternate name (alias) can be
assigned to the major Relay if desired.

Relay Major
m+
Major

Output Relay Minor Alias
Security Level {1}
[SYSTEM/OUT-RLY/ALIAS]

An alternate name (alias) can be
assigned to the Minor Relay if desired.

Relay Minor
m+
Minor

PIN 1 change
Security Level {2}
[SYSTEM/SETUP]

Permanently change password (PIN) that
permits security Level 1 parameter
changes - limited access.

PIN m+

1111

PIN 2 Change
Security Level {2}
[SYSTEM/SETUP]

Permanently change password (PIN) that
permits security Level 2 parameter
changes - unlimited access.

PIN 2 m+

2222