American Power Conversion MX28B200 User Manual
Page 37
MX28B200/400 –48 VDC User’s Manual (990-9133)
Page 31
PARAMETER NAME/
[MENU LOCATION]
DESCRIPTION
DISPLAY SCREENS /
DEFAULT SETTINGS
Firmware Version
{Status Only}
[SYSTEM/SETUP]
Version number of the control unit
firmware.
NOTE: Actual firmware version
number displayed is the current
version as of the date of manufacture.
This parameter cannot be changed.
FW Version +
000189
GMT 1 Alias
Security Level {1}
[MODULES/GMT/ALIAS]
•
•
•
GMT 8 Alias
Security Level {1}
[MODULES/GMT/ALIAS]
An alternate name (alias) that can be
assigned to a GMT Fuse 1 if desired.
•
•
•
An alternate name (alias) that can be
assigned to a GMT Fuse 8 if desired.
GMT 1 m+
-48V
•
•
•
GMT 8 m+
-48V
GMT 1 Blown
Security Level {1}
[MODULES/GMT/SET-ALM]
•
•
•
GMT 8 Blown
Security Level {1}
[MODULES/GMT/SET-ALM]
The Output Relay that is energized when
GMT Fuse 1 is blown.
•
•
•
The Output Relay that is energized when
GMT Fuse 8 is blown.
GMT 1 Alm m+
Major
•
•
•
GMT 8 Alm m+
Major
Hardware Battery Current
Alarm
Security Level {2}
[SYSTEM/SET-ALM]
The output relay energized if there is a
hardware failure in the battery current
monitoring function.
Hw Batt C Almm+
Minor
Hardware Battery Temperature
Alarm
Security Level {2}
[SYSTEM/SET-ALM]
The output relay energized if there is a
hardware failure in the battery
temperature monitoring function.
Hw Batt T Almm+
Minor
Hardware LVD Alarm
Security Level {2}
[SYSTEM/SET-ALM]
The output relay energized if there is a
conflict between the commanded and
sensed positions of the LVD contactor.
Generally the contactor is open when it
should be closed.
Hw LVD Alm m+
Minor
Hardware System Temperature
Alarm
Security Level {2}
[SYSTEM/SET-ALM]
The output relay energized if there is a
hardware failure in the system
temperature monitoring function.
Hw Sys T Alm m+
Minor
Hardware System Voltage
Alarm
Security Level {2}
[SYSTEM/SET-ALM]
The output relay energized if there is a
hardware failure in the system voltage
monitoring function.
Hw Sys V Alm m+
Minor