Vent Termination Locations

The air inlet and exhaust outlet must be installed with

the following minimum clearances (see figure 4):
• Twelve inches above grade or maximum

anticipated snow level.

• Twelve inch minimum clearance on top or four foot

clearance below or to the side of door or

window that may be open.

• Four feet horizontally and vertically from gas

or electric meters, gas regulators, dryer vents,

vent hoods, bathroom fan exhaust, attic fans

and turbines.

• Two feet from an inside corner formed by two

exterior walls.

• Two feet from porches, decks, overhangs and

other obstructions.

**Clearance in accordance with local installation codes and the requirements of the gas supplier.

In addition to maintaining the minimum clearances , the

vent should terminate according to the following guidelines:
1. Use only a 3” concentric vent on the vent termination.

Do not expose any 3” X 2” reducers or bushings to

outdoor ambient temperatures.

2. The air inlet and exhaust outlet must not terminate

under a patio, deck or any covered area.

3. Do not terminate the vent near walkways or into

alleys or other publicly accessible areas.

4. Do not terminate the vent in an area where

children or animals could block pipes.

5. Do not locate the vent terminal too close to shrubs or

bushes.

6. Caulk all cracks, seams and joints within 6 feet

horizontally above and below the vent.

Figure 4

Minimum Termination Clearance for

Outlet Vent

A. 12 in (30 cm) min. clearance above grade,

veranda, porch, deck, balcony, or maximum

anticipated snow level.

B. 12 in. (30 cm) min. clearance on top or 4 ft.

clearance below or to the side of door or window

that may be open.

C. Clearance to permanently closed window.**
D. 12 in (30 cm) min. vertical clearance to ventilated

soffit located above the terminal within a horizontal

distance of 2 ft (61 cm) from the center line of the

terminal.

E. 12 in (30 cm) min. clearance to unventilated soffit.

**Clearance in accordance with local installation codes and the requirements of the gas supplier.

US Installations

F. Clearance to outside corner. **
G. 2 ft (61 cm) clearance to inside corner formed by two

exterior walls.

H. 4 ft (122 cm) clearance to each side of center line

extending above meter/regulator assembly.

I. 4 ft (122 cm) clearance to service regulator vent outlet.
J. 12 in (30 cm) clearance on top or 4 ft (122 cm) clear-

ance below or to the side of nonmechanical air supply

inlet to building or the combustion air inlet to any other

appliance.

K. 3 ft (91 cm) above if within 10 ft (3 m) horizontally of

mechanical air supply inlet.