beautypg.com

Vent pipe installation, Vent pipe length – American Water Heater Power Flex 40-42K BTU User Manual

Page 8

background image

8

Vent Pipe Installation

The following guidelines should be followed when installing

the air inlet and exhaust outlet piping:

Venting should be as direct as possible with a

minimum number of pipe fittings.

Vent diameter must not be reduced unless

specifically noted in the installation instructions.

Support all horizontal pipe runs every four feet

and all vertical pipe runs every six feet or

according to local codes.

Vents run through unconditioned spaces where below

freezing temperatures are expected should be prop-

erly insulated to prevent freezing. For horizontal runs,

wrap the vent pipe with self-regulating 3 or 5 watt heat

tape. The heat tape must be U.L. listed and installed

per the manufacturer’s instructions.

Do not connect this venting system with an existing

vent or chimney.

Do not common vent with the vent pipe of any other

water heater or appliance.

The combustion air inlet and exhaust outlet piping and

termination may be installed in one of the following type

terminations:
1. Standard Horizontal (2 Pipe)

2. Vertical (2 Pipe)

3. Concentric Vent - Through the Wall

All pipe, fittings, pipe cement, primers and procedures

must conform to American National Standard Institute and

American Society for Testing and Materials (ANSI/ASTM)

standards in the United States. This water heater has been

design certified by CSA International for use with the listed

plastic vent pipe material.
IMPORTANT: Do not use vent elbows in this vent pipe

installation (see figure 3 below).

Note: It is important to select the proper pipe cement
for the type plastic pipe being used.

3. Assemble the parts quickly while the cement is still

wet. Twist the pipe 1/4 turn during insertion and hold
for 30 seconds.

Vent Pipe Length

Size the exhaust outlet and combustion air inlet pipes as

specified in Table 3 below. This table lists the maximum

allowable length in feet of the exhaust outlet and combus-

tion air inlet pipes as related to the number of required

elbows and the termination. The specified maximum

lengths are for the separate inlet and exhaust pipe systems

and not the combined length of both systems. Minimum

pipe length is 3 feet with one elbow per side.
1. Determine termination type and pipe size.
2. Determine number of elbows in exhaust pipe (Do not

include elbows in the termination.) Corresponding
number indicates the maximum length of exhaust pipe.

3. Determine number of elbows in inlet pipe. (Do not

include elbows in the termination.) The corresponding
number indicates the maximum length of inlet pipe.

All joints in the inlet and outlet piping must be properly

cemented. Size and cut all piping before cementing.
1. Cut the pipe end square and remove all ragged edges

and burrs. Make sure the inside of the pipe is clean
and free of cuttings and loose dirt. Chamfer the end
and apply primer to the fitting and pipe.

2. Using a suitable grade of pipe cement, apply a moder-

ate, even coat inside the fitting. Apply a liberal amount
of cement to the outside of the pipe to socket depth.

CORRECT FITTINGS

Mesh Metal

Rodent Screen

90° Medium

Sweep Elbow

45° Sweep

Elbow

90° Long

Sweep Elbow

INCORRECT FITTINGS

90° Vent

Elbow

45° Vent

Elbow

Tee Connector

Figure 3
Correct and Incorrect
Pipe Fittings

Table 3 - Maximum Allowable Length in Feet of Exhaust and

Inlet Air Pipe - (42K BTU/Hr models only)

Pipe

Size

(in)

Number of 90° Elbows (medium or long sweep only)

Termination

Options

0

1

2

3

4

5

6

2

40

35

30

25

20

15

10

Std. Horizontal

2

40

35

30

25

20

15

10

Vertical

3

120

115

110

105

100

95

90

Std. Horizontal

3

115

110

105

100

95

90

85

Vertical

Table 4 - Maximum Allowable Length in Feet of Exhaust and

Inlet Air Pipe - (50K/60K BTU/Hr models only)

Pipe

Size

(in)

Number of 90° Elbows (medium or long sweep only)

Termination

Options

0

1

2

3

4

5

6

2

N/A

Std. Horizontal

2

N/A

Vertical

3

45

40

35

30

25

20

15

Std. Horizontal

3

55

50

45

40

35

30

25

Vertical

NOTE:s:
1. N/A - Not Applicable
2. The above maximum lengths are for outlet pipe systems.
3. Maximum of 6 elbows may be used. Use only medium or long
sweep elbows. See figure 8 for details.
4. Two 45° elbows are considered equivalent to one 90° elbow.
5. Minimum length is 3 foot with 1 elbow.
6. Use schedule 40 or 80 CPVC, 40 ABS, or 40 PVC pipe and fittings.

This manual is related to the following products: