Silent Call SD4-SS User Manual
Page 17

17
every 10 seconds. If the detector is in need of maintenance because 
its sensitivity has shifted outside the listed limits, the red LED blinks 
once every 5 seconds. When alarm has been activated by smoke, the 
red LED blinks every 1 second. The LED indication must not be used 
in place of the tests specified under Testing. If the detector senses a 
low battery condition, the red LED blinks once every 45 seconds.
Low Battery Detection
The Model #SD4-SS is powered by a single 3-volt CR123A or 
DL123A Lithium battery (included). The detector checks for a low 
battery at least every 65 minutes. In addition, the red LED of the 
Model #SD4-SS will blink every 45 seconds and the test switch will 
be disabled. This condition will exist for a minimum of 7 days, and 
then the detector’s horn will “chirp” about every 45 seconds. Pressing 
the test switch during this time will silence the chirps for 12 hours. 
The battery should be replaced BEFORE the chirps begin. Be sure to 
replace the battery with a fresh one.
Battery Life Expectancy
Replace the battery once a year or immediately when the low battery
indicator starts to blink and the horn begins to chirp. Replacement 