Hart trimmer calibration – WIKA Pascal 100 User Manual
Page 58
6 Commissioning, operation
58 WIKA Operating Instruction, Pascal 100 and Pascal 100/IS
GB
Pressing YES, the channel is assigned to the selected parameter and the screen with four
channels is displayed again.
6.4.2.8 HART trimmer calibration
When the HART transmitter needs to be recalibrated or adjusted the HART menu can achieve
these two types of possibilities:
-
ADJ.SCL
-
CAL.TRIM
CAL.TRIM permits to correct the analog mA generation, of the HART transmitter, referred to the
digital AO value displayed if the output DAC goes out of tolerance.
Zero and Span needs to be corrected.
If the user wants to recalibrate the Trim. an INPUT mA measurement channel has to configured as
REF channel. In addition, the loop wiring needs to flow to the IN mA terminals.
If no REF mA Input channel is configured first an error will be shown.
- 890.09.2190 (44 pages)
- A-10 (96 pages)
- A2G-50 (52 pages)
- A2G-55 (36 pages)
- AC-1 (88 pages)
- C-2 (24 pages)
- D-10-7 (112 pages)
- D-20-9 (51 pages)
- D-20-9 (35 pages)
- DG-10 (112 pages)
- DP-10 (44 pages)
- DPT-10 (96 pages)
- DPT-10 (92 pages)
- GCS-1 (76 pages)
- HP-2 (84 pages)
- IL-10 (31 pages)
- IPT-10 (56 pages)
- IPT-10 (48 pages)
- IPT-10 (28 pages)
- IPT-10 (36 pages)
- IS-20-F (7 pages)
- IS-20-F (43 pages)
- IS-20-H (7 pages)
- UT-10 (52 pages)
- UT-10 (42 pages)
- IUT-10 (78 pages)
- LH-10 (60 pages)
- LH-20 (60 pages)
- LS-10 (60 pages)
- MG-1 (92 pages)
- MH-1 (11 pages)
- MH-2 (9 pages)
- MHC-1 (84 pages)
- N-10 (35 pages)
- O-10 (108 pages)
- OT-1 (60 pages)
- P-30 (92 pages)
- PSA-31 (124 pages)
- PSD-30 (128 pages)
- R-1 (92 pages)
- S-10 (35 pages)
- S-11 (102 pages)
- S-20 (96 pages)
- S-20 (52 pages)
- SL-1 (21 pages)