WIKA T53 User Manual
Page 5
5
2.0 The Transducer Block
.1 .The .Transducer .Block
contains .all .of .the .manufacturer-specific .parameters .that .define .how .the .T53 .Transmitter .
functions . .Selections .such .as .setting .of .input .type, .engineering .units, .defining .the .dual .func-
tionality .when .using .the .dual .input, .and .so .forth, .are .performed .in .the .Transducer .Block . . .
.
The .transducer .block .in .T53 .allows .the .user .to .select .a .large .number .of .sophisticated .func-
tions . .Therefore, .the .configuration .of .the .transmitter .must .be .carried .out .with .the .greatest .
possible .care . . .
. .The .data .of .the .Transducer .Block .Parameter .List .are .grouped .as .follows:
.8 .AI_TRANSDUCER .Block .
.
.8 .1 . Sensor .characterising .parameters .
.
.8 . . RTD ./ .resistor .specific .parameters .
.
.8 .3 . Thermocouple .specific .parameters .
.
.8 .4 . Output .conditioning .parameters .
.
.8 .5 . Output .parameters .
.
.8 .6 . Diagnostic .parameters .
.
.8 .7 . Sensor .error .detection .parameters .
.
.8 .9 . Sensor .calibration .parameters .
.9 .PR_CUST_LIN .Block .
.
.9 . . Linear .Interpolation .Linearisation .
.
.9 .4 . Custom .Polynomial .linearisation .
.10 .PR_CUST_PRIV .Block .
. .10 .1 . PR_CUST_PRIV .Block .
All .product-specific .parameters .are .set .off .in .grey .background .in .the .TB .Parameter .List . .In .
order .to .configure .these .parameters, .the .files .mentioned .in .the .introduction .must .be .avail-
able .to .the .application .software .
.3 .Default .configuration
WIKA .delivers .the .transmitters .with .at .default .configuration .which .will .suit .the .customer’s .de-
mand .in .many .cases . .The .configuration .task .has .thus .been .reduced .considerably . .
The .individual .default .configurations .are .shown .in .the .TB .Parameter .List, .but .in .short .the .de-
fault .configuration .is .as .follows: .
.Pt100 .acc . .to .the .standard .EN .60 .751 . ( .8 .1 .LIN_TYPE, .value .10) .
.
°C . ( .8 .1 .PRIMARY_VALUE_UNIT, .value .1001) .
.
3-wire .connection . ( .8 . .SENSOR_CONNECTION, .value .1) .
.
Only .sensor .1 . ( .8 .4 .SENSOR_MEAS_TYPE, .value .0) .
.
No .sensor .error .detection . ( .8 .7 .SENSOR_WIRE_CHECK_1, .value .3)
.4 .Your .application .set .up .
In .the .Transducer .block .all .parameters .marked .R ./ .W .can .be .adapted .to .suit .any .mea-
surement .in .temperature, .ohm .or .mV . .The .way .of .presenting .the .file .data .mentioned .in .the .
introduction .varies .greatly .from .one .piece .of .application .software .to .the .other . .Some .pro-
grams .show .drop .down .menus .in .which .the .parameters .must .be .selected .via .text .lines, .while .
other .programs .require .the .user .to .type .in .the .numerical .value .of .the .parameter .selection .