.6 .4 .Measurement .of .thermocouple .with .two .sensors: .
PRIMARY_VALUE_UNIT . . . . . = .K, .°C, .°F .or .°R . .
LIN_TYPE . . . . . . . . . . . . . . . . = .Any .TC . .
LIN_TYPE_ . . . . . . . . . . . . . . = .Any .TC . .
SENSOR_MEAS_TYPE . . . . . . = .Anything, .but .not ."PV .= .SV_1, .SV_ .not .available" . .
SENSOR_CONNECTION . . . . = .N/A .(ignored .in .setup .check) . .
SENSOR_CONNECTION_ . . = .N/A .(ignored .in .setup .check) . .
RJ_TYPE . . . . . . . . . . . . . . . . . = .No .RJ, .Internal, .External .(constant .value) .or .Sensor .-wire .
Connections:
.6 .5 .Measurement .of .combined .sensors .(Sensor .1 .= .TC .and .Sensor . .= .RTD):
PRIMARY_VALUE_UNIT . . . . . = .K, .°C, .°F .or .°R . .
LIN_TYPE . . . . . . . . . . . . . . . . = .Any .TC . .
LIN_TYPE_ . . . . . . . . . . . . . . = .Any .RTD . .
SENSOR_MEAS_TYPE . . . . . . = .Anything, .but .not ."PV .= .SV_1, .SV_ .not .available" . .
SENSOR_CONNECTION . . . . = .N/A .(ignored .in .setup .check) . .
SENSOR_CONNECTION_ . . = .- .or .3-wire . .
RJ_TYPE . . . . . . . . . . . . . . . . . = .No .Reference .Junction, .Internal, .External .(constant .value) . .
Connections:
.6 .6 .Measurement .of .resistance .(linear) .with .one .sensor: .
PRIMARY_VALUE_UNIT . . . . . = .Ohm .or .kOhm . .
LIN_TYPE . . . . . . . . . . . . . . . . = .No .linearisation . .
LIN_TYPE_ . . . . . . . . . . . . . . = .N/A .(ignored .in .setup .check) . .
SENSOR_MEAS_TYPE . . . . . . = .PV .= .SV_1, .SV_ .not .available .
SENSOR_CONNECTION . . . . = .-, .3- .or .4-wire . .
SENSOR_CONNECTION_ . . = .N/A .(ignored .in .setup .check) . .
RJ_TYPE . . . . . . . . . . . . . . . . . = .N/A .(ignored .in .setup .check) .
Connections:
10
Connections .with .two .sensors .
can .be .configured .for . .
.measurements, .difference, .
average .or .redundancy
Connections .with .two .sensors .
can .be .configured .for . .
.measurements, .difference, .
average .or .redundancy