.6 .7 .Measurement .of .resistance .(linear) .with .two .sensors: .
PRIMARY_VALUE_UNIT . . . . . = .Ohm .or .kOhm . .
LIN_TYPE . . . . . . . . . . . . . . . . = .No .linearisation . .
LIN_TYPE_ . . . . . . . . . . . . . . = .No .linearisation . .
SENSOR_MEAS_TYPE . . . . . . = .Anything, .but .not ."PV .= .SV_1, .SV_ .not .available" . .
SENSOR_CONNECTION . . . . = .- .or .3-wire .
SENSOR_CONNECTION_ . . = .Default .set .to .-wire . .
RJ_TYPE . . . . . . . . . . . . . . . . . = .N/A .(ignored .in .setup .check) .
Connections:
.6 .8 .Measurement .of .potentiometer .(linear) .with .one .sensor: .
PRIMARY_VALUE_UNIT . . . . . = .% .
LIN_TYPE . . . . . . . . . . . . . . . . = .No .linearisation . .
LIN_TYPE_ . . . . . . . . . . . . . . = .N/A .(ignored .in .setup .check) . .
SENSOR_MEAS_TYPE . . . . . . = .PV .= .SV_1, .SV_ .not .available . .
SENSOR_CONNECTION . . . . = .3- .or .4-wire . .
SENSOR_CONNECTION_ . . = .N/A .(ignored .in .setup .check) . .
RJ_TYPE . . . . . . . . . . . . . . . . . = .N/A .(ignored .in .setup .check) . .
Connections: .
.6 .9 .Measurement .of .potentiometer .(linear) .with .two .sensors: .
PRIMARY_VALUE_UNIT . . . . . = .% .
LIN_TYPE . . . . . . . . . . . . . . . . = .No .linearisation .
LIN_TYPE_ . . . . . . . . . . . . . . = .No .linearisation .
SENSOR_MEAS_TYPE . . . . . . = .Anything, .but .not ."PV .= .SV_1, .SV_ .not .available" . .
SENSOR_CONNECTION . . . . = .Default .set .to .3-wire . .
SENSOR_CONNECTION_ . . = .Default .set .to .3-wire . .
RJ_TYPE . . . . . . . . . . . . . . . . . = .N/A .(ignored .in .setup .check) . .
Connections:
Connections .with .two .sensors .
can .be .configured .for . .
.measurements, .difference, .
average .or .redundancy
Connections .with .two .sensors .
can .be .configured .for . .
.measurements, .difference, .
average .or .redundancy