WIKA T53 User Manual

Page 25

background image

5

3.2 Analogue Input Blocks (PA Slot 1 & 2) Parameter List, Profibus

Parameter

Rel.

Index Description

Type Store Size

byte

RO /

R/W Min. Max. Default

ST_REV

1

Static .Revision . .Counter .incremented .with .every .parameter .

configuration .change .

Un-

signed .

16

N

RO

0

TAG_DESC

A .user-supplied .description .of .the .block .

Octet .

string

SRC

3

R/W

“ . . . . . .“

STRATEGY

3

Grouping .of .Function .Block . .The .STRATEGY .field .can .be .used .

to .group .blocks .

Un-

signed .

16

SRC

R/W

0

ALERT_KEY

4

Contains .the .identification .number .of .the .plant .unit . .It .helps .to .

identify .the .location .(plant .unit) .of .an .event .

Un-

signed .

8

SRC

1

R/W

0

TARGET_MODE

5

Contains .desired .mode .normally .set .by .a .control .application .or .

an .operator .

Un-

signed .

8

SRC

1

R/W

-

MODE_BLK

6

Contains .the .current .mode .and .the .permitted .and .normal .

mode .of .the .block .

DS-37

D

3

RO

18,15, .

8

ALARM_SUM

7

Contains .the .current .states .of .the .block .alarms .

DS-4

D

8

RO

0;0;0;0

BATCH

8

Intended .to .be .used .in .Batch .applications .in .line .with .

IEC6151 .Part .1 . .Necessary .in .a .distributed .fieldbus .system .to .

identify .used .and .available .channels, .in .addition .used .to .iden-

tify .the .current .batch .in .case .of .alerts .

DS-67 SRC

10

R/W

0;0;0;0

OUT

10

Contains .the .current .measurement .value .in .a .vendor-specific .or .

configuration-adjusted .engineering .unit .and .the .belonging .state .

in .AUTO .MODE .

DS-33

D

5

RO .

**)

Measured .of .

the .variable .

state

PV_SCALE

11

Conversion .of .the .Process .Variable .into .percent .using .the .

high .and .low .scale .values . .The .engineering .unit .of .PV_SCALE .

high .and .low .scale .values .are .directly .related .to .the .PV_UNIT .

of .the .configured .Transducer .Block .(configured .via .Channel .

parameter) . .The .PV_SCALE .high .and .low .scale .values .follow .

the .changes .of .the .PV_UNIT .of .the .related .Transducer .Block .

automatically, .i .e . .a .change .of .the .Transducer .Block .PV_Unit .

causes .no .bump .at .OUT .from .AI .

.* .

Float

SRC

8

R/W

100; .0

OUT_SCALE

1

Scale .of .the .Process .Variable . .Contains .the .values .of .the .lower

limit .and .upper .limit .effective .range, .the .code .number .of .the .

engineering .unit .of .Process .Variable .and .the .number .of .digits .

on .the .right .hand .side .of .the .decimal .point .

DS-36 SRC

11

R/W

100; .0; .

-; .-

LIN_TYPE

13

Type .of .linearisation .

Un-

signed .

8

SRC

1

R/W

0

CHANNEL

14

Reference .to .the .active .Transducer .Block .which .provides .the .

measurement .value .to .the .Function .Block .

Un-

signed .

16

SRC

R/W

1 .: .81 .

.: .83

PV_FTIME

16

Filter .time .of .the .Process .Variable . .Contains .the .time .constant .

for .the .rise .time .of .the .FB .output .up .to .a .value .of .63 .1% .

resulted .from .a .jump .on .the .input .(PT1 .filter) . .The .engineering .

unit .of .the .parameter .is .second .

Float

SRC

4

R/W

0

FSAFE_TYPE

17

Defines .the .reaction .of .the .device .if .a .fault .is .detected . .The .

calculated .ACTUAL .MODE .remains .in .AUTO .

Un-

signed .

8

SRC

1

R/W

1

FSAFE_VALUE

18

Default .value .for .the .OUT .parameter, .if .sensor .or .sensor .elec-

tronic .fault .is .detected . .The .unit .of .this .parameter .is .the .same .

as .the .OUT .unit .

Float

SRC

4

R/W

-

ALARM_HYS

19

Alarm .hysteresis . .To .avoid .triggering .of .many .messages .

Float

SRC

4

R/W

0,5% .of .

range

HI_HI_LIM

1

Value .for .the .upper .limit .of .alarms .

Float

SRC

4

R/W

Max . .

value

HI_LIM

3

Value .for .the .upper .limit .of .warnings .

Float

SRC

4

R/W

Max . .

value

LO_LIM

5

Value .for .the .lower .limit .of .warnings .

Float

SRC

4

R/W

Min .

value

LO_LO_LIM

7

Value .for .the .lower .limit .of .alarms .

Float

SRC

4

R/W

Min . .

value

HI_HI_ALM

30

State .of .the .upper .limit .of .alarms .

DS-39

D

16

RO

0

HI_ALM

31

State .of .the .upper .limit .of .warnings .

DS-39

D

16

RO

0

LO_ALM

3

State .of .the .lower .limit .of .warnings .

DS-39

D

16

RO

0

LO_LO_ALM

33

State .of .the .lower .limit .of .alarms .

DS-39

D

16

RO

0

SIMULATE

34

For .commissioning .and .test .purposes .the .input .value .from .the .

Transducer .Block .in .the .Analogue .Input .Function .Block .AI-FB .

can .be .modified . .This .means .that .the .Transducer .and .AI-FB .

will .be .disconnected .

DS-50 SRC

6

R/W

Disabled

OUT_UNIT_TEXT

35

If .a .specific .unit .of .OUT .parameter .is .not .in .the .code .list .the .

user .has .the .possibility .of .writing .the .specific .text .in .this .para-

meter . .The .unit .code .is .then .equal .to .”textual .unit .definition” .

Octet .

string

SRC

16

R/W

-