1.3 Physical Block (PA Slot 0) Parameter List, Profibus
PARAMETER
Rel . .
Index Description
Type
Store Size R/W Min Max Default
ST_REV
1
Is .incremented .each .time .that .there .is .a .change .in .a .
static .parameter .in .the .physical .block .
Un-
signed .
16
N
RO
0
TAG_DESC
Tag .name .of .the .block . .This .parameter .must .be .unique .
in .the .configuration .
OCTET_
STRING
SRC
3
R/W
‘ .‘
STRATEGY
3
This .can .be .used .to .group .a .Function .Block . .It .is .a .user .
supplied .parameter .for .identification .purpose .
Un-
signed .
16
SRC
R/W
0
ALERT_KEY
4
Current .state .of .alarm .blocks
Un-
signed .
8
SRC
1
R/W
0
TARGET_MODE
5
Current .desired .mode .of .the .block .
Un-
signed .
8
SRC
1
R/W
-
MODE_BLK
6
A .block .has .static .block .parameters, .that .are .not .
changed .by .the .process . .Values .are .assigned .to .this .
parameter .during .the .configuration .or .optimisation . .The .
value .of .ST_REV .must .increase .by .1 .after .every .change .
of .a .static .block .parameter . .This .provides .a .check .of .
the .parameter .revision .
DS-37
D
3
RO
Block .
specific
ALARM_SUM
7
Current .state .of .the .blocks .alarms .
DS-4
D
8
RO
0,0,0,0
SOFTWARE_REVISION
8
Software .revision .of .the .device
VISBLE_
STRING
Cst
16
RO
HARDWARE_REVISION
9
Physical .revision .of .the .device .
VISBLE_
STRING
Cst
16
RO
DEVICE_MAN_ID
10
WIKA .manufacturer .identification .number .
Un-
signed .
16
Cst
RO
0x006B
DEVICE_ID
11
Manufacturer .device .number
VISBLE_
STRING
Cst
16
RO
WIKA .
5310
DEVICE_SER_NUM
1
Device .serial .number
VISBLE_
STRING
Cst
16
RO
DIAGNOSIS
13
Bit .string .indicating .the .diagnosis .of .the .device . .See .
Diagnosis
OCTET_
STRING
D
4
RO
DIAGNOSIS_EXTENSION
14
Not .used .
OCTET_
STRING
D
6
RO
DIAGNOSIS_MASK
15
Not .used .
OCTET_
STRING
Cst
4
RO
DIAGNOSIS_MASK_EXTENSION
16
Not .used .
OCTET_
STRING
Cst
6
RO
DEVICE_CERTIFICATION
17
PA .device .certification
VISBLE_
STRING
Cst
3
RO
WRITE_LOCKING
18
If .Locked, .no .writes .from .anywhere .are .allowed, .except .
to .clear .WRITE_LOCK . .Cyclic .block .inputs .will .continue .
to .be .updated .
Un-
signed .
16
N
R/W
FACTORY_RESET
19
Factory .reset: .
.
1: . Restart .with .default .
. 506: . Restart .processor .
. 71: . Recover .default .address .to .the .device
Un-
signed .
16
SRC
R/W
DESCRIPTOR
0
It .is .a .user .supplied .description .of .the .block .in .the .
application .
OCTET_
STRING
SRC
3
R/W
DEVICE_MESSAGE
1
It .is .a .user .supplied .Message .of .the .block .in .the .appli-
cation . .
OCTET_
STRING
SRC
3
R/W
DEVICE_INSTAL_DATE
Date .of .the .device .installation .
OCTET_
STRING
SRC
16
R/W
LOCAL_OP_ENA
3
Not .Used .
Un-
signed .
8
N
1
R/W
1
IDENT_NUMBER_SELECT
4
.
0: . Profile .specific .Ident_Num .
.
1: . Manufacture .specific .Ident_Number .
.
: . Manufacture .specific .Ident_Number .of .V .0 .
.
3: . Ident_Number .of .Multi_Variable .device
Un-
signed .
8
SRC
1
R/W
HW_WRITE_PROTECTION
5
Unimplemented
RESERVED
6-3 Reserved .to .PNO .(PROFIBUS .Nutzerorganisation)