1.3 Physical Block (PA Slot 0) Parameter List, Profibus

PARAMETER

Rel . .

Index Description

Type

Store Size R/W Min Max Default

ST_REV

1

Is .incremented .each .time .that .there .is .a .change .in .a .

static .parameter .in .the .physical .block .

Un-

signed .

16

N

RO

0

TAG_DESC

Tag .name .of .the .block . .This .parameter .must .be .unique .

in .the .configuration .

OCTET_

STRING

SRC

3

R/W

‘ .‘

STRATEGY

3

This .can .be .used .to .group .a .Function .Block . .It .is .a .user .

supplied .parameter .for .identification .purpose .

Un-

signed .

16

SRC

R/W

0

ALERT_KEY

4

Current .state .of .alarm .blocks

Un-

signed .

8

SRC

1

R/W

0

TARGET_MODE

5

Current .desired .mode .of .the .block .

Un-

signed .

8

SRC

1

R/W

-

MODE_BLK

6

A .block .has .static .block .parameters, .that .are .not .

changed .by .the .process . .Values .are .assigned .to .this .

parameter .during .the .configuration .or .optimisation . .The .

value .of .ST_REV .must .increase .by .1 .after .every .change .

of .a .static .block .parameter . .This .provides .a .check .of .

the .parameter .revision .

DS-37

D

3

RO

Block .

specific

ALARM_SUM

7

Current .state .of .the .blocks .alarms .

DS-4

D

8

RO

0,0,0,0

SOFTWARE_REVISION

8

Software .revision .of .the .device

VISBLE_

STRING

Cst

16

RO

HARDWARE_REVISION

9

Physical .revision .of .the .device .

VISBLE_

STRING

Cst

16

RO

DEVICE_MAN_ID

10

WIKA .manufacturer .identification .number .

Un-

signed .

16

Cst

RO

0x006B

DEVICE_ID

11

Manufacturer .device .number

VISBLE_

STRING

Cst

16

RO

WIKA .

5310

DEVICE_SER_NUM

1

Device .serial .number

VISBLE_

STRING

Cst

16

RO

DIAGNOSIS

13

Bit .string .indicating .the .diagnosis .of .the .device . .See .

Diagnosis

OCTET_

STRING

D

4

RO

DIAGNOSIS_EXTENSION

14

Not .used .

OCTET_

STRING

D

6

RO

DIAGNOSIS_MASK

15

Not .used .

OCTET_

STRING

Cst

4

RO

DIAGNOSIS_MASK_EXTENSION

16

Not .used .

OCTET_

STRING

Cst

6

RO

DEVICE_CERTIFICATION

17

PA .device .certification

VISBLE_

STRING

Cst

3

RO

WRITE_LOCKING

18

If .Locked, .no .writes .from .anywhere .are .allowed, .except .

to .clear .WRITE_LOCK . .Cyclic .block .inputs .will .continue .

to .be .updated .

Un-

signed .

16

N

R/W

FACTORY_RESET

19

Factory .reset: .

.

1: . Restart .with .default .

. 506: . Restart .processor .

. 71: . Recover .default .address .to .the .device

Un-

signed .

16

SRC

R/W

DESCRIPTOR

0

It .is .a .user .supplied .description .of .the .block .in .the .

application .

OCTET_

STRING

SRC

3

R/W

DEVICE_MESSAGE

1

It .is .a .user .supplied .Message .of .the .block .in .the .appli-

cation . .

OCTET_

STRING

SRC

3

R/W

DEVICE_INSTAL_DATE

Date .of .the .device .installation .

OCTET_

STRING

SRC

16

R/W

LOCAL_OP_ENA

3

Not .Used .

Un-

signed .

8

N

1

R/W

1

IDENT_NUMBER_SELECT

4

.

0: . Profile .specific .Ident_Num .

.

1: . Manufacture .specific .Ident_Number .

.

: . Manufacture .specific .Ident_Number .of .V .0 .

.

3: . Ident_Number .of .Multi_Variable .device

Un-

signed .

8

SRC

1

R/W

HW_WRITE_PROTECTION

5

Unimplemented

RESERVED

6-3 Reserved .to .PNO .(PROFIBUS .Nutzerorganisation)