beautypg.com

Safety – WIKA T32.xS User Manual

Page 11

background image

GB

11

WIKA safety manual temperature transmitter T32.xS

11583631.03 08/2014 GB/D/F/E

WARNING!

With certain device-side diagnosed hardware errors, the instrument gives

a downscale error signal with a loop current of < 3.8 mA, but can however,

for technical reasons, also ensure no signal ≤ 3.6 mA with the appropriate

configuration. The evaluation system must therefore interpret a loop

current of < 3.8 mA as a fault condition.

With certain inadmissible configurations (e.g. with deactivated write protection) the

transmitter likewise generates an error signal. In order to find the reason behind the

error signal, the diagnostic functions available over HART

®

should be used. Such

functions are offered, for example, in the WIKA_T32 configuration software (free

download from www.wika.com).

2.5 Write protection

The T32.xS offers a write protection functionality in order to prevent accidental

configuration changes. The write-protection password is factory set to “0”.

A T32.xS temperature transmitter with SIL option will only work once the

write protection has been activated. Without write protection activated,

such a transmitter will signal an error.

2.5.1 Operation of the write protection

The write protection function is activated via a passsword (numbers in the range 0 to

65535 are allowed) and a switch (activate/deactivate write protection).

A change in the state of the write protection switch is only possible after the successful

input of the password. The password can be altered via its own menu.

CAUTION!

There is no possibility of retrieving a forgotten password! The only

possibility is for the password to be reset at the factory!

Also, activation of the write protection is only possible through the input of

the correct password!

2. Safety