WIKA Operating Instructions Differential Pressure Transmitter DELTA-trans

4

1. Safety instructions

The appropriate national safety regulations (i.e. VDE 0100 /

EN 60 079-14 / EN 837-2) must be observed when installing,

commissioning and operating these instruments.

Do not work on the gauge while it is powered

Serious injuries and/or damage can occur should the appropriate regulations

not be observed

Only appropriately qualified personnel should work on these instruments

2. Operating principle

The differential pressure transmitter consists mainly of a mechanical measu-
ring system (1) with an elastic pressure element (2), a Hall-effect sensor (3) with
signal processing board (4) and a case with the connections for the electronics.

A magnet (5), rigidly coupled to the
pressure element, influences the
electromagnetic field of the HALL-
effect sensor. The resulting signal is
amplified to a standard output signal
via the signal processing board.

For recalibration, zero and span
can be adjusted by means of easily
accessible potentiometers (6).

Pressure entries are identified by the
symbols; j high pressure and i low
pressure