Starting, operation gb – WIKA WU-26 User Manual

Page 12

background image

12

WIKA Operating instructions/Betriebsanleitung/Mode d'emploi/Instrucciones de servicio, WU-2X

11553678.02 GB/D/F/E 10/2012

Current output (2-wire)

4 ... 20 mA:

RA ≤ (U+ – 10 V) / 0,02 A
Voltage output (3-wire)

0 ... 5 V:

RA > 5 kOhm

0 ... 10 V:

RA > 10 kOhm

with RA in Ohm and U+ in Volt

Current for external display- or evaluation equipment can be supplied directly from the circuit, when operat-

ing a transducer with current output. A voltage drop specific to the display unit is to be considered. The

UHP-display unit of type (N)WUR-1 has a specific voltage drop of 6 V. The transducers are short-circuit-proof

for a short time, but anyhow any incorrect connection of the instrument should be avoided.

WARNING!

For equipment with Ex nA nL certification, or if operated under nA nL conditions: Do not

separate when energized.

For products with FM Approval: The connection between cable and connector shall

withstand a tensile force of min. 15 N

The transducer is designed to operate with an input voltage of 10 ... 31 VDC / 14 ... 31 with output signal

0 ... 10 V. The voltage value Ui = 31 VDC shall not be exceeded in the current loop circuit. The interrelation-

ship between voltage supply and load resistor (RA) is illustrated by the following diagram.

Signal output and allowed load

4 ... 20 mA, 2-wire

7. Starting, operation

GB

permitted range