Faults – WIKA PSA-31 User Manual

Page 29

background image

29

WIKA operating instructions pressure switch model PSA-31

GB

14018458.01 11/2011 GB/D/F/E

8. Faults

In the event of any faults, first check whether the pressure switch is mounted correctly, mechanically and

electrically.

Error display

Via the instrument's display internal errors are output.

The following table shows the error codes and their meaning.

8. Faults

Problem

Possible cause

Measure

No output signal

Cable break

Check the continuity

No output signal

No/wrong power supply

Rectify the power supply

No/wrong output signal

Wiring error

Observe the pin assignment

Constant output signal upon change in

pressure

Mechanical overload caused by overpressure Replace instrument; if it fails repeatedly, contact

the manufacturer

Deviating zero point signal

Overpressure limit exceeded

Observe the permissible overpressure limit

Signal span too small

Mechanical overload caused by overpressure Replace instrument; if it fails repeatedly, contact

the manufacturer

Signal span too small

Power supply too high/low

Rectify the power supply

Signal span drops

Humidity has entered

Assemble the cable correctly

Signal span drops/too small

Diaphragm damaged, e.g. due to impacts,

abrasive/aggressive medium; corrosion at

diaphragm/process connection

Contact manufacturer and replace instrument

If complaint is unjustified, we will charge you the complaint processing fees.

Error

Description

ATT1

On changing the switch point, the system automatically reduces the reset point.

ATT2

Zero-point adjustment error, current pressure is outside the limits

ATT3

Password entered for menu access is incorrect

ERR

Internal error

OL

Overpressure, measuring range exceeded > approx. 5% (display blinks)

UL

Underpressure, below measuring range < approx. 5 % (display blinks)

Acknowledgement of an error display by pressing the "Enter" key.