Commissioning, operation, 7 menu (programming and factory setting), Factory setting – WIKA PSA-31 User Manual

Page 21

background image

21

WIKA operating instructions pressure switch model PSA-31

GB

14018458.01 11/2011 GB/D/F/E

6. Commissioning, operation

6.7 Menu (programming and factory setting)

Display mode

Long press on menu key

Programming mode

Factory setting:

SP1 / FH1

Value

(Min: MBA +0.5 %

Max: MBE)

Instrument nominal pressure

RP1 / FL1

Value

(Min: MBA

Max: SP1 -0.5 %)

Instrument nominal pressure -10 %

SP2 / FH2

Value

(Min: MBA +0.5 %

Max: MBE)

Instrument nominal pressure

RP2 / FL2

Value

(Min: MBA

Max: SP2 -0.5 %)

Instrument nominal pressure -10 %

EF

RES

Yes / No

Reset to factory setting

DS1

Value

0 ... 50 s

0 s

DR1

Value

0 ... 50 s

0 s

DS2

Value

0 ... 50 s

0 s

DR2

Value

0 ... 50 s

0 s

OU1

PARA

HNO, HNC, FNO, FNC

HNO

OU2

PARA

HNO, HNC, FNO, FNC

HNO

UNIT

Unit

BAR, MPA, KPA, PSI, KG/cm2

Order-related

0SET

Yes / No

Zero Point adjustment 3% of span

0 s

ACT, HIGH, LOW, OFF, SP1/FH1,

RP1/FL1, SP2/FH2, RP2/FL2

ACT

DISM

PARA

DISU

Value

1/2/5/10 update/second

0 s

DISR

Yes / No

Rotate display by 180°

RHL

Yes / No

Reset HIGH, LOW

PAS

Value

Password

without

TAG

Value

Measuring point number

without

Legend:

MBA = Start of measuring range

MBE = End of measuring range

END

END