Commissioning, operation, 7 menu (programming and factory setting), Factory setting – WIKA PSA-31 User Manual
Page 21
21
WIKA operating instructions pressure switch model PSA-31
GB
14018458.01 11/2011 GB/D/F/E
6. Commissioning, operation
6.7 Menu (programming and factory setting)
Display mode
Long press on menu key
Programming mode
Factory setting:
SP1 / FH1
Value
(Min: MBA +0.5 %
Max: MBE)
Instrument nominal pressure
RP1 / FL1
Value
(Min: MBA
Max: SP1 -0.5 %)
Instrument nominal pressure -10 %
SP2 / FH2
Value
(Min: MBA +0.5 %
Max: MBE)
Instrument nominal pressure
RP2 / FL2
Value
(Min: MBA
Max: SP2 -0.5 %)
Instrument nominal pressure -10 %
EF
RES
Yes / No
Reset to factory setting
DS1
Value
0 ... 50 s
0 s
DR1
Value
0 ... 50 s
0 s
DS2
Value
0 ... 50 s
0 s
DR2
Value
0 ... 50 s
0 s
OU1
PARA
HNO, HNC, FNO, FNC
HNO
OU2
PARA
HNO, HNC, FNO, FNC
HNO
UNIT
Unit
BAR, MPA, KPA, PSI, KG/cm2
Order-related
0SET
Yes / No
Zero Point adjustment 3% of span
0 s
ACT, HIGH, LOW, OFF, SP1/FH1,
RP1/FL1, SP2/FH2, RP2/FL2
ACT
DISM
PARA
DISU
Value
1/2/5/10 update/second
0 s
DISR
Yes / No
Rotate display by 180°
RHL
Yes / No
Reset HIGH, LOW
PAS
Value
Password
without
TAG
Value
Measuring point number
without
Legend:
MBA = Start of measuring range
MBE = End of measuring range
END
END