6. Commissioning, operation

6.6 Parameters

Parameter

Description

SP1/SP2

Hysteresis function: Switch point switching output (1 or 2)

FH1/FH2

Window function: Window high switching output (1 or 2)

RP1/RP2

Hysteresis function: Reset point switching output (1 or 2)

FL1/FL2

Window function: Window low switch output (1 or 2)

EF

Extended programming functions

RES

Return the set parameter to the factory settings

DS1/DS2

Switch delay time, which must occur without interruption before any electrical signal change occurs (SP1 or SP2)

DR1/DR2

Switch delay time, which must occur without interruption before any electrical signal change occurs (RP1 or RP2)

OU1

Switching function switching output (1 or 2)

OU2

HNO = hysteresis function, normally open

HNC = hysteresis function, normally closed

FNO = window function, normally open

FNC = window function, normally closed

UNIT

Changing units

(If the measuring range is outside the indication range, a unit switching is not possible and the UNIT parameter is not

indicated)

0SET

Offset adjustment (3 % of span)

DISM

Display value in display mode

ACT = actual pressure value; LOW, HIGH = minimum, maximum temperature value OFF = display off;

SP1/FH1 = function switch point 1, RP1/FL1 = function reset point 1,

SP2/FH2 = function switch point 2, RP2/FL2 = function reset point 2

DISU

Display update 1, 2, 5, 10 updates/second

DISR

Rotate display indicator by 180°

RHL

Clear the Min- and Max-value memories

PAS

Password input, 0000 = no password

Password input digit by digit

TAG

Input of a 16-figure alphanumeric measuring point number