WIKA operating instructions pressure switch model PSA-31
GB
14018458.01 11/2011 GB/D/F/E
6. Commissioning, operation
Index
(decimal)
Object name
Value Remarks
2
RES
130
Return the set parameter to the factory settings
2
LOCK
163
General keylock On
2
UNLOCK
164
General keylock Off
2
RHL
176
Clear the Min- and Max-value memories
2
0SET
177
Zero-point adjustment (3 % of span) see page 17
Index
(decimal)
Object
name
Format
Access Value range
Factory set-
ting
Remarks
240
MBA
32 Bit IEEE
754 Float
R
-
1,000
The pressure value is
always linearised such
that the MBA equals the
value 1,000 and the MBE
equals the value 9,000.
241
MBE
32 Bit IEEE
754 Float
R
-
9,000
The pressure value is
always linearised such
that the MBA equals the
value 1,000 and the MBE
equals the value 9,000.
250
DISR
8 Bit
Enumeration
R/W
0 = Standard
1 = 180° rotated
0
Turn display indicator
by 180°
251
DISM
8 Bit
Enumeration
R/W
0 = Act
1 = HIGH
2 = LOW
3 = SP1/FH1
4 = RP1/FL1
5 = SP2/FH2
6 = RP2/FL2
7 = Off
0
Display value in display
mode
252
PAS
16 Bit
unsigned
R/W
0 … 9,999
-
Enter password in order
to set the parameters at
the instrument. Password
0 = no password
253
LOCK
8 Bit
Enumeration
R/W
0 = Unlocked
1 = Locked
0
General keylock