Commissioning, operation – WIKA PSA-31 User Manual

Page 27

background image

27

WIKA operating instructions pressure switch model PSA-31

GB

14018458.01 11/2011 GB/D/F/E

6. Commissioning, operation

Index

(decimal)

Object name

Value Remarks

2

RES

130

Return the set parameter to the factory settings

2

LOCK

163

General keylock On

2

UNLOCK

164

General keylock Off

2

RHL

176

Clear the Min- and Max-value memories

2

0SET

177

Zero-point adjustment (3 % of span) see page 17

Index

(decimal)

Object

name

Format

Access Value range

Factory set-

ting

Remarks

240

MBA

32 Bit IEEE

754 Float

R

-

1,000

The pressure value is

always linearised such

that the MBA equals the

value 1,000 and the MBE

equals the value 9,000.

241

MBE

32 Bit IEEE

754 Float

R

-

9,000

The pressure value is

always linearised such

that the MBA equals the

value 1,000 and the MBE

equals the value 9,000.

250

DISR

8 Bit

Enumeration

R/W

0 = Standard

1 = 180° rotated

0

Turn display indicator

by 180°

251

DISM

8 Bit

Enumeration

R/W

0 = Act

1 = HIGH

2 = LOW

3 = SP1/FH1

4 = RP1/FL1

5 = SP2/FH2

6 = RP2/FL2

7 = Off

0

Display value in display

mode

252

PAS

16 Bit

unsigned

R/W

0 … 9,999

-

Enter password in order

to set the parameters at

the instrument. Password

0 = no password

253

LOCK

8 Bit

Enumeration

R/W

0 = Unlocked

1 = Locked

0

General keylock