Dynamic behaviour output
Run-up time approx.
10 s
90 %
100 %
10 %
t
t
T
A
t
t
S
2
1
Fig. 10: Sudden change of the process variable. t
T
: dead time; t
A
: rise time; t
S
: jump response time
1
Process variable
2
Output signal
Dead time
≤
150 ms
Rise time
≤
100 ms (10 … 90 %)
Step response time
≤
250 ms (ti: 0 s, 10 … 90 %)
Damping (63 % of the input variable)
0 … 999 s, adjustable
Input variable
Adjustment
Adjustment range of the min./max. adjustment relating to the nominal measuring range:
-
Min.
-5 … +95 %
-
Max.
-5 … +105 %
Adjustment range of the zero/span adjustment relating to the nominal measuring range:
-
zero
-5 … +95 %
-
Span
-5 … +105 %
Recommended max. turn down
10 : 1 (no limitation)
Nominal measuring ranges and overload resistance
Nominal range
Overload capacity, max.
pressure
Overload capacity, min.
pressure
Gauge pressure
0 … 0.4 bar/0 … 40 kPa
2 bar/200 kPa
-1 bar/-100 kPa
0 … 1.6 bar/0 … 160 kPa
10 bar/1000 kPa
-1 bar/-100 kPa
0 … 16 bar/0 … 1.6 MPa
80 bar/8 MPa
-1 bar/-100 kPa
0 … 40 bar/0 … 4 MPa
80 bar/8 MPa
-1 bar/-100 kPa
38
Process pressure transmitter IPT-1* Vers. 3.0 - metalic sensor • 4 … 20 mA