Page 38

background image

Dynamic behaviour output

Run-up time approx.

10 s

90 %

100 %

10 %

t

t

T

A

t

t

S

2

1

Fig. 10: Sudden change of the process variable. t

T

: dead time; t

A

: rise time; t

S

: jump response time

1

Process variable

2

Output signal

Dead time

150 ms

Rise time

100 ms (10 … 90 %)

Step response time

250 ms (ti: 0 s, 10 … 90 %)

Damping (63 % of the input variable)

0 … 999 s, adjustable

Input variable

Adjustment

Adjustment range of the min./max. adjustment relating to the nominal measuring range:

-

Min.

-5 … +95 %

-

Max.

-5 … +105 %

Adjustment range of the zero/span adjustment relating to the nominal measuring range:

-

zero

-5 … +95 %

-

Span

-5 … +105 %

Recommended max. turn down

10 : 1 (no limitation)

Nominal measuring ranges and overload resistance

Nominal range

Overload capacity, max.
pressure

Overload capacity, min.
pressure

Gauge pressure

0 … 0.4 bar/0 … 40 kPa

2 bar/200 kPa

-1 bar/-100 kPa

0 … 1.6 bar/0 … 160 kPa

10 bar/1000 kPa

-1 bar/-100 kPa

0 … 16 bar/0 … 1.6 MPa

80 bar/8 MPa

-1 bar/-100 kPa

0 … 40 bar/0 … 4 MPa

80 bar/8 MPa

-1 bar/-100 kPa

38

Process pressure transmitter IPT-1* Vers. 3.0 - metalic sensor • 4 … 20 mA

9 Supplement

37300

-EN

-100302